CIRCUTOR CVM144 Series User Manual
Page 21

----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 20
6.- SET-UP PROCEDURE
The set-up procedure of the CVM-144 is performed by means of several SET-
UP options.
For accessing the set-up menu the keys max & min must be
simultaneously pressed once the instrument is at the main screen.
When accessing the SET-UP, the message "SET-UP unlo " (1) is shown for
some seconds on screen, or, otherwise, the message "SET-UP loc" (2).
(1) Set-up UNLO (SET-UP unlocked ) : when the SET-UP is
accessed, configuration parameters can be either visualized and
modified.
(2) Set-up LOC (SET-UP locked ) : when the SET-UP is accessed,
configuration parameters can be visualized but cannot be modified .
Once into the SET-UP, use the keyboard to select different options and enter
required variables:
- The key
validates de value and pass to the next menu.
- The key MAX permits to select among different options in a menu, or to
increase a digit when a variable is being entered.
- The key MIN permits to move the cursor along the digits.
Different options are following shown in a sequential mode:
1. Choice of visualization of phase-to-neutral or phase-to-phase voltages
2. Voltage displaying format
3. Voltage transformation ratio.
4. Value of the current transformer primary : 1 a 10000 A
5. Value of the current primary value for the measurement of neutral and
residual currents.
6. Power demand meter setting
7. Choice of default initial screen
8. Time for display shutdown
9. Deleting energy counters
10. Choice of harmonic distortion determination mode: d% or THD%
11. Alarms setting : RELAY 1 (OUT 1) & RELAY 2 (OUT 2)
12. Analog outputs and inputs setting