----- Supply network analyzer CVM 96 ---------- ------- Page No. 5
3.- INSTALLATION AND START-UP
The manual you hold in your hands contains information and
warnings that the user should respect in order to guarantee a proper
operation of all the instrument functions and keep its safety
conditions. The instrument must not be powered and used until its
definitive assembly on the cabinet’s door.
Whether the instrument is not used as manufacturer’s specifications, the
protection of the instrument can be damaged.
When any protection failure is suspected to exist (for example, it presents
external visible damages), the instrument must be immediately powered off. In this
case contact a qualified service representative.
3.1.- Installation.
Before powering the instrument for the first time, verify following points:
a.-
Power supply: see rear part of your CVM 96
Standard supply :
Single-phase 230 V
∼
(a.c.)
- Frequency
: 50 - 60 Hz
- Supply voltage tolerance : - 10 % / + 15
- Connection terminal : Terminals 1 - 2 (Power supply)
- Burden
: 5 VA
SDC Model
: 0.24.... 120 V c.c. ( continua )
- Supply voltage tolerance : - 20 % / + 15
- Connection terminal : Terminals 1 - 2 (Power supply)
- Burden
: 2,2 W
On request: other voltages