CIRCUTOR CVM96 Series User Manual
Page 27

----- Supply network analyzer CVM 96 ---------- ------- Page No. 26
- For accessing to the next option, press "
": SETUP options for the second relay
will appear (only with CVM 96...-C2).
OUT 2
RELAY 2
CODE
00
Parameter value (2)
Act as before. Pressing again "
" the SETUP mode is exited.
b.- ALARM conditions (1 condition for each relay): If any other parameter (1 to 30)
is selected at (1), two outputs can be configured as alarms. For each output it is
possible to set:
Any of the parameters measured by the CVM 96
MAXIMUM value
MINIMUM value
Delay for the conditions
These screens are successively displayed by the CVM 96 once the parameter
has been selected ( for the SETUP of each option proceed as in the Section a.-):
b.1.- Programming the maximum value to be controlled:
OUT 1
RELAY 1
AL hI
0.000
Maximum value
The key "max" will increase the value of the blinking digit (0,1...9, sign -- ).
Use the key "min" to pass to the following digit.