----- Supply network analyzer CVM 96 ---------- ------- Page No. 4
By means of an internal microprocessor it simultaneously measures:
Parameter
Symbol
L1
L2 L3
Average
Voltage (phase-neutral)
V
x x x
Voltage (phase-phase)
V
x x x
Current
A
x x x
xx
Frequency
Hz
x
Active power
kW
x x x
x
Reactive power L
kvarL
x x x
x
Reactive power C
kvarC
x x x
x
Apparent power
xx
Power factor
PF
x x x
x
Cos
ϕ
xx
Power demand
Pd
x
kW h
energy
x
kvarhL
energy
x
kvarhC
energy
x
Neutral current
I
N
xx
Voltage THD
% THD- V
x x x
Current THD
% THD- A
x x x
Individual harmonic current
content (Up to the 15
th
)
xx xx xx
Available: x: Display and communications xx: Communications
The CVM 96 delivers the visualization of above listed parameters by means of
three 4-digit, led type, displays. Up to 3 parameters can be simultaneously read in
the screen.
---------------------------------------------------------------------------------------------
OTHER FEATURES
- Low-size (96 x 96 mm), panel-mounting analyzer.
- True R.M.S. measuring system.
- Instantaneous, maximum and minimum values of each measured parameter.
- Energy measurement (indication through a lighting led)
- RS-485 or RS-232 type communication to a PC (optional)