Unit installation, Prior recommendations, Installation – CIRCUTOR CVM-C5 Series User Manual
Page 7

3�- UNIT INSTALLATION
3.1.- PRIOR RECOMMENDATIONS
In order to use the unit safely, it is critical that individuals who handle it follow
the safety measures described in the standards of the country where it is being
used, use the necessary personal protective equipment, and pay attention to
the various warnings indicated in this instruction manual.
The
CVM-C5 unit must be installed by authorised and qualified staff.
The power supply plug must be disconnected and measuring systems switched off before
handling, altering the connections or replacing the unit. It is dangerous to handle the unit
while it is powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal
injury and damage to installations.
The manufacturer of the unit is not responsible for any damage resulting from failure by the
user or installer to heed the warnings and/or recommendations set out in this manual, nor for
damage resulting from the use of non-original products or accessories or those made by other
manufacturers.
In the event an anomaly or malfunction is detected in the unit, refrain from using it to take any
measurements.
Inspect the work area before taking any measurements. Do not take measurements in dan-
gerous areas or where there is a risk of explosion.
Disconnect the unit from the power supply (unit and measuring system power
supply) before maintaining, repairing or handling the unit's connections.
Please contact the after-sales service if you suspect that there is an operational
fault in the unit.
3.2.- INSTALLATION
The unit will be installed on a panel (92
+0.8
x 92
+0.8
mm panel drill hole, in compliance with DIN
43700). All connections are located inside the electric panel.
Terminals, opening covers or removing elements can expose parts that are
hazardous to the touch while the unit is powered. Do not use the unit until it is
fully installed.
The unit must be connected to a power circuit that is protected with gl (IEC 269) or M type
fuses with a rating of 0.5 to 2 A. It must be fitted with a circuit breaker or equivalent device,
in order to be able to disconnect the unit from the power supply network.
7
Instruction Manual
CVM-C5