5 programmable output – Applied Motion TXM24IP-1EG User Manual
Page 21

21
Rev. C
920-0089
TXM24 Ethernet Hardware Manual
3.4.5 Programmable Output
The TXM24 drives feature one optically isolated digital output (OUT). This output can be set to
automatically control a motor brake, to signal a fault condition, to indicate when the motor is in
position or to provide an output frequency proportional to motor speed (tach signal). Or the output
can be turned on and off by program instructions like Set Output (SO). The output can be used to
drive LEDs, relays and the inputs of other electronic devices like PLCs and counters. The OUT+
(collector) and OUT- (emitter) terminals of the transistor are available at the connector. This allows
the output to be configured for current sourcing or sinking.
Diagrams of various connection types follow.
Do not connect the output to more than 30 volts. The current through the output terminal
must not exceed 100mA.
+
-
OUT+
OUT-
5 - 24
volt DC
Power
Supply
Connecting a Sinking Output
Load
TXM24
COM
IN
OUT+
OUT-
PLC
Connecting a Sourcing Output
5 - 24VDC
Power Supply
TXM24
+
-
+
-
5 - 24
volt DC
Power
Supply
Driving a Relay
OUT+
OUT-
relay
1N4935 suppresion diode
TXM24