Introduction, Presentation – ABUS Technologies A1500 Universal Process Indicator User Manual
Page 4

ABUS TECHNOLOGIES INC.
4
A1500
1. INTRODUCTION
A1500 is a universal process indicator which accepts a large variety of input
signals and sensors. A six-digit LED display shows measured value and all
programming parameters. Instrument configuration is achieved from the keyboard,
without any hardware change. Thus, the selection of input type and type of alarms
action, besides other special functions, are accessed and defined from the frontal
keyboard. The user should read this manual thoroughly before using the instrument. It
must be handled with care and should be used accordingly for best results.
2. PRESENTATION
Technical Parameters
Power:
85 to 265Vac/dc, 50/60 Hz (basic model);
24 Vdc/ac, optional;
Maximum consumption:
VA
Relays:
ALM1 and ALM2: SPDT - 3A / 250Vac (3A / 30Vdc);
ALM3 and ALM4: SPST – NA 3A / 250Vac (3A / 30Vdc) (optional);
All input signals are factory calibrated. Thermocouples are calibrated according to NBS standards
(NBR12771), RTD’s NBR 13773/97 (IEC-751), (
=0.00385).
Internal resolution:
128000 levels,
Display resolution:
62000 levels (-31000 to 31000)
Sampling rate:
5 measurements per second for TC and RTD
measurements for 0-50mA, 4-20mA, 0-5V, 0-10V
Accuracy:
Thermocouples J, K, T, N: ± 0.25% of full scale +1°C.
Thermocouples E, R, S, B: ± 0.25% of full scale +3°C.
Pt100: 0.2% of full scale
Current or voltage: 0.15% of full scale
Cold junction compensation error: ± 1 °C
Warm up time:
15 minutes
Input impedance:
0-50mV, Pt100 and T/C: >10M
0-5V, 0-10V > 1M
4-20mA: 15
Pt100 measure:
3-wire circuit, 750A excitation current.
PV retransmission resolution: 4000 levels, 550max.
Working conditions:
0 to 55°C, 35 to 85% relative humidity.
Front panel:
IP65, Polycarbonate UL94 V-2;
Back panel:
IP30, ABS+PC UL94 V-0;
Weight:
240g basic version; 265g with options
Dimension:
48×96×92 mm
Panel cut out:
45×93mm