1. INTRODUCTION

A1500 is a universal process indicator which accepts a large variety of input

signals and sensors. A six-digit LED display shows measured value and all

programming parameters. Instrument configuration is achieved from the keyboard,

without any hardware change. Thus, the selection of input type and type of alarms

action, besides other special functions, are accessed and defined from the frontal

keyboard. The user should read this manual thoroughly before using the instrument. It

must be handled with care and should be used accordingly for best results.

2. PRESENTATION



Technical Parameters

Power:

85 to 265Vac/dc, 50/60 Hz (basic model);

24 Vdc/ac, optional;

Maximum consumption:

VA

Relays:

ALM1 and ALM2: SPDT - 3A / 250Vac (3A / 30Vdc);

ALM3 and ALM4: SPST – NA 3A / 250Vac (3A / 30Vdc) (optional);

All input signals are factory calibrated. Thermocouples are calibrated according to NBS standards

(NBR12771), RTD’s NBR 13773/97 (IEC-751), (

=0.00385).

Internal resolution:

128000 levels,

Display resolution:

62000 levels (-31000 to 31000)

Sampling rate:

5 measurements per second for TC and RTD

measurements for 0-50mA, 4-20mA, 0-5V, 0-10V

Accuracy:

Thermocouples J, K, T, N: ± 0.25% of full scale +1°C.

Thermocouples E, R, S, B: ± 0.25% of full scale +3°C.

Pt100: 0.2% of full scale

Current or voltage: 0.15% of full scale

Cold junction compensation error: ± 1 °C

Warm up time:

15 minutes

Input impedance:

0-50mV, Pt100 and T/C: >10M

0-5V, 0-10V > 1M

4-20mA: 15

Pt100 measure:

3-wire circuit, 750A excitation current.

PV retransmission resolution: 4000 levels, 550max.

Working conditions:

0 to 55°C, 35 to 85% relative humidity.

Front panel:

IP65, Polycarbonate UL94 V-2;

Back panel:

IP30, ABS+PC UL94 V-0;

Weight:

240g basic version; 265g with options

Dimension:

48×96×92 mm

Panel cut out:

45×93mm