8. OPERATION


For best results, this indicator requires correct setting of parameters as input

type (T/C, Pt100, 4-20mA, etc), alarms triggering point, alarm function, etc. These

parameters are divided in five levels or groups of parameters which we will refer to as

Cycles.

S.NO.

CYCLE

ACCESS

1

Work

Free Access

2

Alarms

3

Functions

4

Configuration

Reserved Access

5

Customized

Linearization

6

Calibration

Table-4: Parameter Cycles

The work cycle has free access. All other cycles require a certain combination

of key strokes to be accessed. The combination is

and

keys, when pressed

simultaneously within the cycle chosen, just press

to go to the subsequent

parameters of this cycle. At the end of each cycle the display will go back to the work

cycle.

After reaching the intended prompt just press

or

key to change this

parameter accordingly. All changes are recorded in non-volatile memory as we move

to next prompt. After 25 seconds with no key pressed the indicator will return to the

measuring cycle (work cycle).

8.1 Configuration Protection

As safety measure, changes can be prevented by a combination of keys for each cycle. The

protected parameters could be still viewed but not changed.

To protect a cycle, just press

and

keys simultaneously for 3 seconds, at the

beginning of the referred cycle.

To unlock this cycle just press the same keys again for 3 seconds. The display will briefly flash

confirming that the cycle was locked or unlocked.

For further protection, the unlock operation through the keypad may be disabled by changing

the position of an internal strap inside the indicator:

When PROT is OFF, the user is allowed to lock and unlock the cycles using the keypad as

explained above.

If PROT is ON, the cycles lock/unlock operation is disable.