Heat of extraction data, Clw quad series chiller installation manual – WaterFurnace CLW Chiller User Manual
Page 20
20
CLW QUAD SERIES CHILLER INSTALLATION MANUAL
Heat of Extraction Data
Model
Source
GPM
Load
GPM
EST
Heat Of Extraction (HE)
ºF
105°F
110°F
115°F
120°F
125°F
060
180
180
50
864.6
847.6
837.4
827.6
823.8
55
920.0
910.6
901.2
889.2
877.4
60
992.4
978.4
962.6
955.6
941.6
65
1062.0
1046.0
1035.8
1021.0
1003.2
080
240
240
50
1145.4
1129.0
1116.4
1111.4
1098.4
55
1226.4
1219.6
1201.6
1185.4
1169.8
60
1323.0
1304.2
1283.4
1276.2
1255.2
65
1426.8
1405.0
1380.8
1361.6
1337.6
100
300
300
50
1366.0
1360.6
1343.2
1329.0
1312.4
55
1462.6
1455.4
1436.8
1418.4
1398.2
60
1577.8
1556.4
1546.0
1524.8
1503.2
65
1701.0
1676.4
1664.0
1639.0
1613.8
120
360
360
50
1762.6
1743.6
1723.0
1700.8
1693.8
55
1892.0
1867.4
1857.4
1833.2
1807.2
60
2043.6
2014.8
1986.6
1973.6
1945.8
65
2189.2
2156.8
2140.8
2108.6
2076.8
140
420
420
50
1937.4
1910.0
1885.8
1876.0
1850.0
55
2077.2
2065.0
2033.2
2004.8
1974.2
60
2244.2
2211.6
2179.0
2159.2
2126.4
65
2405.0
2387.0
2349.6
2312.0
2287.6
07/24/13