CLW QUAD SERIES CHILLER INSTALLATION MANUAL

Control Features

Alarm Outputs

The control has 18-enumerated status variable for each

compressor and the unit.

• Compressor

Lockout

Any compressor can be locked out from the local

display or using the HOA switch.

Motor & Oil Thermal Overload

The motor thermal overload switch is a normally

closed (NC) switch that monitors the temperature of

the motor.

This safety can be configured to auto reset or manual

reset (factory default).

Motor Rotation Direction

The motor rotation direction switch is a normally

closed (NC) switch that monitors the rotation direction

of the motor.

Electrical Thermal Overload

The electrical thermal overload switch is a normally

closed (NC) switch that monitors the electrical thermal

conditions of the wires leaving the main contactor.

This safety can be configured to auto reset or manual

reset (factor default).

Flow Switches

The optional flow switches are normally closed (NC)

switch that monitors the flow in the pipes into the

evaporator and condenser.

This safety clears when flow is present.

Freeze Protection

The optional freeze protection switch is a normally

closed (NC) switch that monitors the temperature of

the water in the pipe coming out of the evaporator for

freeze conditions.

This safety can be configured to auto reset or

manual reset.

Low Refrigerant Saturation Temperatures

The controller monitors the refrigerant saturation

temperatures for low saturation temperatures. Without

glycol, it is recommend to set the low saturation

temperature to 34°F and consider it an alarm condition

it the saturation temperature continuously remains

below that temperature for 90 seconds.

The compressor will not restart until the low saturation

compressor delay time delay has been satisfied.

High Refrigerant Saturation Temperatures

The controller monitors the refrigerant saturation

temperatures for high saturation temperatures. An

alarm condition occurs if the saturation temperature

exceeds the high limit.

The compressor will not restart until the high saturation

compressor delay time delay has been satisfied.