Electrical Data
MCA (Maximum Current Rating) is a calculation based off the RLA of the compressor on the electrical connection
and is used to properly size the wire. Please refer to NEC for additional information.
MOCP (Maximum Over Current Protection) is a calculation based off the RLA of the compressor on the electrical
connection and is used to fuses and breakers. Please refer to NEC for additional information.
Notes:
1.
Where RLA1 is equal to the largest compressor in the system and the others RLA's are all subsequent
motors present in the system.
2.
Total unit MCA shall not exceed 500A or a second connection will be required.
Model
Rated
Voltage
Voltage
Min/Max
HP
Compressor
Unit
MCC
RLA1
MOA
MCA
HP
MOCP
060
208-230/60/3
187/253
15
89.9
57.6
77.3
244.8
60
302.4
460/60/3
414/506
43.0
27.6
35.0
117.3
144.9
575/60/3
517/633
34.4
22.0
28.0
93.5
115.5
080
208-230/60/3
187/253
20
110.7
70.9
108.0
301.3
80
372.2
460/60/3
414/506
54.1
34.7
48.8
147.5
182.2
575/60/3
517/633
43.3
27.8
39.1
118.2
146.0
100
208-230/60/3
187/253
25
132.8
85.1
117.7
361.7
100
446.8
460/60/3
414/506
63.5
40.7
53.2
173.0
213.7
575/60/3
517/633
50.8
32.6
42.6
138.6
171.2
120
208-230/60/3
187/253
30
165.6
106.2
145.1
451.4
120
557.6
460/60/3
414/506
82.8
53.1
65.6
225.7
278.8
575/60/3
517/633
66.3
42.5
52.5
180.6
223.1
140
208-230/60/3
187/253
35
160.4
102.8
165.8
436.9
140
539.7
460/60/3
414/506
80.2
51.4
75.0
218.5
269.9
575/60/3
517/633
64.2
41.1
60.0
174.7
215.8
11/05/13