Low voltage wiring, Clw quad series chiller installation manual, Low voltage panel layout – WaterFurnace CLW Chiller User Manual
Page 12
12
CLW QUAD SERIES CHILLER INSTALLATION MANUAL
Low Voltage Wiring
WIRE LEGEND
(TB-P7): 120VAC Power (Comp 3&4)
(TB-P12): 24 VAC Power (Circuit 1 & 2)
(TB-P5): 120 VAC switch power
(TB-P11): 24 VAC switch power
(TB-P16):24VDC switch power
(TB-P13): 24 VAC Power (Circuit 3 & 4)
(TB-P8): 120 VAC Neutral (Comp 1&2)
(TB-P9): 120VAC Neutral (Comp 3&4)
(TB-P14): 24 VAC Neutral (Circuit 1 & 2)
(TB-P15): 24 VAC Neutral (Circuit 3 & 4)
(TB-P17): 24 VDC Power (Circuit 1 & 2)
(TB-P20): 24 VDC Neutral (Circuit 3 & 4)
(TB-P10): 120VAC Ground
(TB-P2): 120 VAC Power (Outlets & Heaters)
(TB-P1): 120 VAC switch power
(TB-P3): 120 VAC Neutral (Outlets & Heaters)
(TB-P4): 120 VAC Ground
(Outlets)
(TB
-P
6
)
(TB-P6): 120 VAC Power (Comp 1&2)
(TB-P19): 24 VDC Neutral (Circuit 1 & 2)
(Outlets)
(TB-P2)
(RIB-2.1 & Outlets)
(R
-3
.13
, TB-
B
22
)
(RIB-
7
.1
)
(RIB
-1
.1
)
INPUT/OUTPUT SIGNAL
INPUT/OUTPUT COMMON
120VAC, 24VAC
120VAC (+) / 24VDC (-)
GROUND
24VAC & 24VDC (+)
BLACK
WHITE
GREEN
RED
BLUE
GRAY
(R
-9
.13
, TB
-Y
22
)
(KMC
-U
1
,2
,3
)
(K
MC
-U
4
,5
,6
&
TB-
O
1
9
)
(KMC
-U
1
,2
,3
)
(KMC
-U
4
,5,
6
& TB
-B
20
)
(U2
-C
-5
, U
3
-C
-5
)
(U5
-C
-5,
U6-
C
-5
)
(TB
-O
4
)
ETHERNET WIRE
(TB-P18): 24 VDC Power (Circuit 3 & 4)
10A
10A
5A
1A
120 VAC POWER
24 VAC POWER 24 VDC POWER
COMPRESSOR 2 SENSORS
WATER TEMP SENSORS & CONTROL VALVES
(120
VAC
Transformer
)
(24
V
AC
Transformer)
(24
V
DC
Transformer)
(120
VAC
Transformer)
120VAC 15A Duplex
Receptacle
(T
B
-G
4
)
COMPRESSOR 1 SENSORS
(TB
-P12
)
(TB
-P
1
7
)
LOW VOLTAGE PANEL LAYOUT
UNIT TYPE:
UNIT MODEL:
SERIAL NUMBER:
Touch Screen IP: ________________________ (Assigned)
Master Controller IP: _____________________ (Assigned)
Chipkin Field Server IP:___________________ (Assigned)
START-UP DATE:
START-UP TECHNICIAN:
CHILLIT CHILLERS LLC
PH: (574) 970-3035
Rev: E
08/01/13
CPM
© CHILLIT CHILLERS 2013
(TB-B19):Isolation Valves (24VAC)
(TB-B20):Isolation Valve (common)
(TB-B10) +24 VAC
(T
B
-B11
, U
1
-G
-16
)
(TB-B1): Evaporator Inlet C1&C2
(TB-B2): Common TBG1 & 3
(TB-B3): Evaporator Outlet Temp C1&C2
(U1-IN1-1)
(U1-C-2)
(U1-IN2-3)
(TB-B9): Evaporator Outlet Temp C3&C4
(TB-B8): Common TBG8&10
(TB-B21):C1&2 Isolation Valves Signal
(TB-B22): C3&4 Isolation Valve Signal
(TB-B18): Condenser Header Outlet Temp
(TB-B17): Common TBG20
(TB-O1): C1-Condenser Liquid Temp
(TB-O2): Common TBG1 & 3
(TB-O3): C1-Evaporator Gas Temp
(TB-O4): C1-Discharge Pressure
(TB-O5): C1-Discharge Pressure
(TB-O10): C1- Motor Protect Alarm
(TB-O12): C1-High Pressure Alarm
(TB-O13): C1-Low Pressure ALarm
(TB-O6): C1-Suction Pressure
(TB-O8): C1-Current Transducer
(TB-O9): C1-Current Transducer
(TB-O7): C1-Suction Pressure
(R-1.14)
(R-3.14)
(R-4.14)
(U2-IN1-1)
(U2-IN2-3)
(U1-IN3-4)
(U2-IN4-6)
(TB-P17) +24vDc
(TB-O4) +24vDc
(TB-Y1): C2-Condenser Liquid Temp
(TB-Y2): Common TBG1 & 3
(TB-Y3): C2-Evaporator Gas Temp
(TB-Y4): C2-Discharge Pressure
(TB-Y5): C2-Discharge Pressure
(TB-Y10): C2-Motor Protect
(TB-Y12): C2-High Pressure Alarm
(TB-Y13): C2-Low Pressure Alarm
(TB-Y6): C2-Suction Pressure
(TB-Y8): C2-Current Transducer
(TB-Y9): C2-Current Transducer
(TB-Y7): C2-Suction Pressure
(R-5.14)
(R-7.14)
(R-8.14)
(U3-IN1-1)
(U3-C-2)
(U3-IN2-3)
(U3-IN3-4)
(U3-IN4-6)
(TB-O8) +24vDc
(TB-Y4) +24vDc
(U2-IN5-7)
(TB
-O
6
) +
24
vDc
(U3-IN5-7)
(TB-Y6) +24vDc
(TB-Y11): C2-Thermal Overload Alarm
(TB-O11): C1- Thermal Overload Alarm
(R-2.14)
(R-6.14)
COMPRESSOR 4 SENSORS
COMPRESSOR 3 SENSORS
(TB-G1): C3-Condenser Liquid Temp
(TB-G2): Common TBG1 & 3
(TB-G3): C3-Evaporator Gas Temp
(TB-G4): C3-Discharge Pressure
(TB-G3): C3-Discharge Pressure
(TB-G10): C3- Motor Protect Alarm
(TB-G12): C3-High Pressure Alarm
(TB-G13): C3-Low Pressure ALarm
(TB-G6): C3-Suction Pressure
(TB-G8): C3-Current Transducer
(TB-G9): C3-Current Transducer
(TB-G7): C3-Suction Pressure
(R-9.14)
(R-11.14)
(R-12.14)
(U5-IN1-1)
(U5-C-2)
(U5-IN2-3)
(U5-IN3-4)
(U5-IN4-6)
(TB-P18) +24vDc
(TB-G4) +24vDc
(TB-N1): C4-Condenser Liquid Temp
(TB-N2): Common TBG1 & 3
(TB-N3): C4-Evaporator Gas Temp
(TB-N4): C4-Discharge Pressure
(TB-N5): C4-Discharge Pressure
(TB-N10): C4-Motor Protect
(TB-N12): C4-High Pressure Alarm
(TB-N13): C4-Low Pressure Alarm
(TB-N6): C4-Suction Pressure
(TB-N8): C4-Current Transducer
(TB-N9): C4-Current Transducer
(TB-N7): C4-Suction Pressure
(R-13.14)
(R-15.14)
(R-16.14)
(U6-IN1-1)
(U6-C-2)
(U6-IN2-3)
(U6-IN3-4)
(U6-IN4-6)
(TB-G8) +24vDc
(TB-N4) +24vDc
(U5-IN5-7)
(TB
-G6
)
+24
vDc
(U6-IN5-7)
(TB-N6) +24vDc
(TB-N11): C4-Thermal Overload Alarm
(TB-G11): C3- Thermal Overload Alarm
(R-10.14)
(R-14.14)
(TB-Z1): Enable Compressor 1
(TB-Z3): 120 VAC Neutral
(TB-Z5): Enable Compressor 2
(RIB-1.2)
(RIB-2.2)
(TB-Z2): Enable Heat Comp1
(TB-Z6): 120 VAC Neutral
(TB-Z7): Enable Heat Comp2
(RIB-3.2)
(RIB-4.2)
(TB-Z4): Reset Compressor 1
(TB-Z9): 120 VAC Neutral
(TB-Z8): Reset Compressor 2
(RIB-5.2)
(RIB-6.2)
(TB-P9)
(TB-Z3)
(TB-Z6)
(TB-Z19): Ground
(TB-Z10): Enable Compressor 3
(TB-Z12): 120 VAC Neutral
(TB-Z14): Enable Compressor 4
(TB-Z11): Enable Heat Comp3
(TB-Z15): 120 VAC Neutral
(TB-Z16): Enable Heat Comp4
(TB-Z13): Reset Compressor 3
(TB-Z18): 120 VAC Neutral
(TB-Z17): Reset Compressor 4
ENABLE COMPRESSORS & RESET
RIB-2
Heater C1
RIB-5
Heater C2
RIB-3
Reset C1
RIB-6
Reset C2
(TB-P2_120V+)
(RIB-2.1_120V+)
(TB-Z8)
(TB-Z4)
(TB-Z7)
(TB-Z2)
RIB-1
Enable C1
RIB-4
Enable C2
(TB
-P
6
)
(TB-Z5)
(TB-Z1)
(RIB-4.1_120V+)
(RIB-1.1_120V+)
(RIB-3.1_120V+)
(U2-G-4 & RIB-2.5)
(U2-OUT1-1)
(U3-G-4)
(U3-OUT1-1)
(RIB-1.5)
(U2-OUT2-3)
(U3-G-4)
(U
3
-OUT
2
-3
)
(U
2
-G
-8
)
(U
2-
O
U
T4-
7
)
(U3-G-8)
(U3-OUT4-7)
RIB-8
Heater C3
RIB-11
Heater C4
RIB-9
Reset C3
RIB-12
Reset C4
(R
IB-5
.1
_1
2
0
V
+)
(RIB-8.1_120V+)
(TB-Z8)
(TB-Z4)
(TB-Z7)
(TB-Z2)
RIB-7
Enable C3
RIB-10
Enable C4
(TB-P7)
(TB-Z5)
(TB-Z1)
(RIB-10.1_120V+)
(RIB-7.1_120V+)
(R
IB
-9
.1_
120
V
+)
(U5-G-4)
(U5-OUT1-1)
(U6-G-4)
(U6-OUT1-1)
(U5-G-4)
(U5-OUT2-3)
(U6-G-4)
(U6-OUT2-3)
(U5-G-8)
(U5-OUT4-7)
(U6-G-8)
(U6-OUT4-7)
1
(TB-Y10)
(R-4.13)
(TB-Y12)
(R-6.13)
(TB-Y13)
(R-7.13)
R-5
[120VAC]
Comp-2
Motor
P
rotect
Alarm
R-7
[120VAC]
Comp-2
High
Pressure
Alarm
R-8
[120VAC]
Comp-2
Low
Pressure
Alarm
(TB-O10)
(TB-P11)
(TB-O12)
(R-2.13)
(U2-IN6-9)
(U2-IN7-10)
(TB-O13)
(R-3.13)
(U2-IN8-12)
5(NO)
13(-)
9
1(NC)
14(+)
R-1
[120VAC]
Comp-1
Motor
P
rotect
Alarm
R-3
[120VAC]
Comp-1
High
Pressure
Alarm
R-4
[120VAC]
Comp-1
Low
Pressure
Alarm
(U2-C-11)
(R-2.5)
(R-3.5)
(U3-IN6-9)
(U3-IN7-10)
(U3-IN8-12)
(U3-C-11)
(R-6.5)
(R-7.5)
R-6
[120VAC]
Comp-2
Thermal
Overload
Alarm
(TB-O11)
(R-1.13)
(U2-IN6-9)
R-2
[120VAC]
Comp-1
Thermal
Overload
Alarm
(R-1.5)
(TB-Y11)
(R-5.13)
(U3-IN6-9)
(TB-B1)
(TB-B2)
(eSC-1)
(eSC-3)
(eSC-2)
(TB-B3)
(TB-B4)
(TB-B5)
(TB-B6)
(TB-B13)
(TB-B14)
NOTE: Pressure sensors &
CT’s require resistors and DIP switches
(TB-P14)
(TB-P12)
(TB-P19)
(U1-IN1-1)
(U1-C-2)
(U1-IN2-3)
(U1-IN3-4)
(U1-C-5)
(U1-IN4-6)
(U1-IN5-7)
(U1-C-8)
(U1-IN6-9)
(U1-IN7-10)
(U1-C-11)
(U1-IN8-12)
Evap Inlet (Return) Temp C1 C2
Common IN1 & IN2
Evap Outlet (Supply) Temp C1 C2
Cond Inlet (Return) Temp C1 C2
Common IN3 & IN4
Cond Outlet (Supply) Temp C1 C2
Evap/Cond Flow Switch C1 C2
Common IN5 & IN6
[A]
[A]
Common IN7 & IN8
[A]
Input ID
U1 -A
U1 +B
U1 ϛ
U1 24Vac c
U1 24Vac -
U1 24Vac +
[A]
[A]
Common Out1 & Out2
[A]
[A]
Common Out3 & Out4
Output ID
[A]
Evap/Cond Iso 2-Way C1 C2
Common Out5 & Out6
[A]
[A]
U1-OUT1-1
U1-OUT2-3
U1-G-4
U1-OUT3-5
U1-OUT4-7
U1-G-8
U1-OUT5-9
U1-OUT6-11
U1-G-12
U1-OUT7-13
U1-OUT8-15
Common Out5 & Out6
U1-G-16
U1 – MASTER TEMPS C1 & C2
(U2-IN1-1)
(U2-C-2)
(U2-IN2-3)
(U2-IN3-4)
(U2-C-5)
(U2-IN4-6)
C1-Condenser Liquid Temp
Common IN1 & IN2
C1-Evaporator Gas Temp
C1- Discharge Pressure
Common IN3 & IN4
Input ID
C1-Suction Pressure
(U2-IN5-7)
(U2-C-8)
(U2-IN6-9)
(U2-IN7-10)
(U2-C-11)
(U2-IN8-12)
C1-Current Transducer (CT)
Common IN5 & IN6
C1-Motor+ Thermal Alarm
C1-High Pressure Alarm
Common IN7 & IN8
C1- Low Pressure Alarm
C1 – Enable Compressor
C1 – Crank Heater
Common Out1 & Out2
Not Used
C1 – Momentary Reset
Common Out3 & Out4
Output ID
Not Used
Not Used
Common Out5 & Out6
Not Used
Not Used
U2-OUT1-1
U2-OUT2-3
U2-G-4
U2-OUT3-5
U2-OUT4-7
U2-G-8
U2-OUT5-9
U2-OUT6-11
U2-G-12
U2-OUT7-13
U2-OUT8-15
Common Out5 & Out6
U2-G-16
U2 - COMPRESSOR 1
(TB-P14)
(TB-P12)
(TB-Z19)
U2 24Vac c
U2 24Vac -
U2 24Vac +
(U1 +B)
(U1
ϛ)
(U1 -A)
U2 -A
U2 +B
U2 ϛ
(U3-IN1-1)
(U3-C-2)
(U3-IN2-3)
(U3-IN3-4)
(U3-C-5)
(U3-IN4-6)
C2-Condenser Liquid Temp
Common IN1 & IN2
C2-Evaporator Gas Temp
C2-Discharge Pressure
Common IN3 & IN4
Input ID
C2-Suction Pressure
(U3-IN5-7)
(U3-C-8)
(U3-IN6-9)
(U3-IN7-10)
(U3-C-11)
(U3-IN8-12)
C2-Current Transducer (CT)
Common IN5 & IN6
C2- Motor + Thermal Alarm
C2-High Pressure Alarm
Common IN7 & IN8
C2-Low Pressure Alarm
C2 – Enable Compressor
C2- Crank Heater
Common Out1 & Out2
Not Used
C2 – Momentary Reset
Common Out3 & Out4
Output ID
Not Used
Not Used
Common Out5 & Out6
Not Used
Not Used
U3-OUT1-1
U3-OUT2-3
U3-G-4
U3-OUT3-5
U3-OUT4-7
U3-G-8
U3-OUT5-9
U3-OUT6-11
U3-G-12
U3-OUT7-13
U3-OUT8-15
Common Out5 & Out6
U3-G-16
U3 - COMPRESSOR 2
(TB-P14)
(TB-P12)
(TB-Z19)
U3 24Vac c
U3 24Vac -
U3 24Vac +
U3 -A
U3 +B
U3 ϛ
250
Ω
250
Ω
250
Ω
250
Ω
250
Ω
250
Ω
(U2 +B)
(U2
ϛ)
(U2 -A)
-
-
-
-
-
R-
NOTE: Pressure sensors &
CT’s require resistors and DIP switches
(U4-IN1-1)
(U4-C-2)
(U4-IN2-3)
(U4-IN3-4)
(U4-C-5)
(U4-IN4-6)
(U4-IN5-7)
(U4-C-8)
(U4-IN6-9)
(U4-IN7-10)
(U4-C-11)
(U4-IN8-12)
Evap Inlet (Return) Temp C3 C4
Common IN1 & IN2
Evap Outlet (Supply) TempC3 C4
Cond Inlet (Return) Temp C3 C4
Common IN3 & IN4
Cond Outlet (Supply) Temp C3 C4
Evap/Cond Flow Switch C3 C4
Common IN5 & IN6
[A]
Evap Header Outlet Temp
Common IN7 & IN8
Cond Header Outlet Temp
Input ID
U4 -A
U4 +B
U4 ϛ
U4 24Vac c
U4 24Vac -
U4 24Vac +
[A]
[A]
Common Out1 & Out2
[A]
[A]
Common Out3 & Out4
Output ID
[A]
Evaporator Iso 2-Way C3 C4
Common Out5 & Out6
Condenser Iso 2-way C3 C4
[A]
U4-OUT1-1
U4-OUT2-3
U4-G-4
U1-2-OUT3-5
U4-OUT4-7
U4-G-8
U4-OUT5-9
U4-OUT6-11
U4-G-12
U4-OUT7-13
U4-OUT8-15
Common Out5 & Out6
U4-G-16
U4 – MASTER TEMPS C3 & C4
(U5-IN1-1)
(U5-C-2)
(U5-IN2-3)
(U5-IN3-4)
(U5-C-5)
(U5-IN4-6)
C3-Condenser Liquid Temp
Common IN1 & IN2
C3-Evaporator Gas Temp
C3- Discharge Pressure
Common IN3 & IN4
Input ID
C3-Suction Pressure
(U5-IN5-7)
(U5-C-8)
(U5-IN6-9)
(U5-IN7-10)
(U5-C-11)
(U5-IN8-12)
C3-Current Transducer (CT)
Common IN5 & IN6
C3-Motor+ Thermal Alarm
C3-High Pressure Alarm
Common IN7 & IN8
C3- Low Pressure Alarm
C3 – Enable Compressor
C3 – Crank Heater
Common Out1 & Out2
Not Used
C3 – Momentary Reset
Common Out3 & Out4
Output ID
Not Used
Not Used
Common Out5 & Out6
Not Used
Not Used
U5-OUT1-1
U5-OUT2-3
U5-G-4
U5-OUT3-5
U5-OUT4-7
U5-G-8
U5-OUT5-9
U5-OUT6-11
U5-G-12
U5-OUT7-13
U5-OUT8-15
Common Out5 & Out6
U5-G-16
U5 - COMPRESSOR 3
U5 24Vac c
U5 24Vac -
U5 24Vac +
U5 -A
U5 +B
U5 ϛ
(U6-IN1-1)
(U6-C-2)
(U6-IN2-3)
(U6-IN3-4)
(U6-C-5)
(U6-IN4-6)
C4-Condenser Liquid Temp
Common IN1 & IN2
C4-Evaporator Gas Temp
C4-Discharge Pressure
Common IN3 & IN4
Input ID
C4-Suction Pressure
(U6-IN5-7)
(U6-C-8)
(U6-IN6-9)
(U6-IN7-10)
(U6-C-11)
(U6-IN8-12)
C4-Current Transducer (CT)
Common IN5 & IN6
C4- Motor + Thermal Alarm
C4-High Pressure Alarm
Common IN7 & IN8
C4-Low Pressure Alarm
C4 – Enable Compressor
C4- Crank Heater
Common Out1 & Out2
Not Used
C4 – Momentary Reset
Common Out3 & Out4
Output ID
Not Used
Not Used
Common Out5 & Out6
Not Used
Not Used
U6-OUT1-1
U6-OUT2-3
U6-G-4
U6-OUT3-5
U6-OUT4-7
U6-G-8
U6-OUT5-9
U6-OUT6-11
U6-G-12
U6-OUT7-13
U6-OUT8-15
Common Out5 & Out6
U6-G-16
U6 - COMPRESSOR 4
U6 24Vac c
U6 24Vac -
U6 24Vac +
U6 -A
U6 +B
U6 ϛ
250
Ω
250
Ω
250
Ω
250
Ω
250
Ω
250
Ω
(TB-N10)
(R-12.13)
(TB-N12)
(R-14.13)
(TB-N13)
(R-15.13)
R-13
[120VAC]
Comp-4
Motor
P
rotect
Alarm
R-15
[120VAC]
Comp-4
High
Pressure
Alarm
R-16
[120VAC]
Comp-4
Low
Pressure
Alarm
(TB-G10)
(R-8.13)
(TB-G12)
(R-10.13)
(U5-IN6-9)
(U5-IN7-10)
(TB-G13)
(R-11.13)
(U5-IN8-12)
R-9
[120VAC]
Comp-3
Motor
Protect
Alarm
R-11
[120VAC]
Comp-3
High
Pressure
Alarm
R-12
[120VAC]
Comp-3
Low
Pressure
Alarm
(U5-C-11)
(R-10.5)
(R-11.5)
(U6-IN6-9)
(U6-IN7-10)
(U6-IN8-12)
(U6-C-11)
(R-14.5)
(R-15.5)
R-14
[120VAC]
Comp-4
Thermal
Overload
Alarm
(TB-G11)
(R-9.13)
(U5-IN6-9)
R-10
[120VAC]
Comp-3
Thermal
Overload
Alarm
(R-9.5)
(TB-N11)
(R-13.13)
(U6-IN6-9)
(TB-B10): Condenser Inlet (Return) C1&C2
(TB-B4): Condenser Inlet (Return) C1&C2
(TB-B5): Common TBG4,5 & 7
(TB-B6): Cond Outlet (Supply) Temp C1&C2
(U1-IN3-1)
(U1-C-5)
(U1-IN4-6)
(TB-B7): Evaporator Inlet C3&C4
(TB-B12): Cond Outlet (Supply) Temp C1&C2
(TB-B13): Evap & Cond Flow Switch C1&C2
(TB-B15): Evap & Cond Flow Switch C3&C4
(TB-B16): Evaporator Header Outlet Temp
(TB-B14): Common TBG11,12,14,15
TB
TB
2
2
R
TB
2-
R
TB
2
R
T
R
T
R
3
T
R
3-
T
3-
TB
5
R
TB
5
R
TB
5
R-
TB
R-
TB
R-
6
TB
6
TB
6-
R
TB
6-
R-
(RIB-7.2)
(RIB-8.2)
(RIB-9.2)
(RIB-10.2)
(RIB-11.2)
(RIB-12.2)
(TB-Z9)
(TB-Z12)
(TB-Z15)
(TB-B11): Common TBG11,12,14,15
(U4-IN1-1)
(U4-C-2)
(U4-IN2-3)
(U4-IN3-1)
(U4-C-5)
(U4-IN4-6)
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
13(-)
9
14(+)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
5(NO)
1(NC)
(R-5.1)
(R-13.5)
(TB-O1)
(TB-O2)
(TB-O3)
(TB-O5)
TB-P19(24VDC-)
(TB-O7)
(TB-O9)
(U2-C-5)
(R-1 & 2.9)
(R-4.9)
(R-1.5)
(R-3.9)
(TB-Y1)
(TB-Y2)
(TB-Y3)
(TB-Y5)
TB-P19(24VDC-)
(TB-Y7)
(TB-Y9)
(U3-C-5)
(R-5 & 6.9)
(R-8.9)
(R-5.5)
(R-7.9)
(TB-B7)
(TB-B8)
(TB-B9)
(TB-B10)
(TB-B11)
(TB-B12)
(TB-B15)
(TB-B14)
(TB-B18)
(TB-B17)
(U4 +B)
(U4
ϛ)
(U4 -A)
(U5 +B)
(U5
ϛ)
(U5 -A)
(TB-B16)
(TB-G1)
(TB-G2)
(TB-G3)
(TB-G5)
TB-P20(24VDC-)
(TB-G7)
(TB-G9)
(U5-C-5)
(R-9 & 10.9)
(R-12.9)
(R-9.5)
(R-11.9)
(TB-N1)
(TB-N2)
(TB-N3)
(TB-N5)
TB-P20(24VDC-)
(TB-N7)
(TB-N9)
(U6-C-5)
(R-13 & 14.9)
(R-16.9)
(R-13.5)
(R-15.9)
EOL - ON
EOL – OFF
EOL – OFF
EOL – OFF
EOL – OFF
EOL – OFF
(U1-IN5-7)
(U1-C-8 & U4-C-8)
(U4-IN5-7)
(U4-IN7-10)
(U4-C-11)
(U4-IN8-12)
(RIB-1.4)
(RIB-1.5)
(RIB-2.4)
(RIB-3.5)
(RIB-3.4)
(TB-B21)
(TB-B20)
(RIB-4.4)
(RIB-4.5)
(RIB-5.4)
(RIB-6.5)
(RIB-6.4)
(TB-P15)
(TB-P13)
(TB-Z19)
(TB-P15)
(TB-P13)
(TB-Z19)
(RIB-7.4)
(RIB-7.5)
(RIB-8.4)
(RIB-9.5)
(RIB-9.4)
(TB-B22)
(U1-G-16)
(RIB-10.4)
(RIB-10.5)
(RIB-11.4)
(RIB-12.5)
(RIB-12.4)
(TB-P15)
(TB-P13)
(TB-Z19)
(U3 +B)
(U3
ϛ)
(U3 -A)
(U1-OUT7-13)
(U4-OUT7-13)