Table 14. Data format definitions
Selected
Actual Signal Limits
Count Limits
Data Format
Input Range
Min.
Max.
Min.
Max.
Engineering Units
±
10 V
-10.25 V
+10.25 V
-10250
+10250
0–10 V
-0.50 V
+10.25 V
-500
+10250
0–5 V
-0.50 V
+5.50 V
-500
+5500
1–5 V
+0.50 V
+5.50 V
+500
+5500
0–20 mA
0.0 mA
+20.5 mA
0
+20500
4–20 mA
+3.5 mA
+20.5 mA
+3500
+20500
Scaled for PID
➂
±
10 V
-10 V
+10 V
0
+16383
0–10 V
0 V
+10 V
0
+16383
0–5 V
0 V
+5 V
0
+16383
1–5 V
+1 V
+5 V
0
+16383
0–20 mA
0 mA
+20 mA
0
+16383
4–20 mA
+4 mA
+20 mA
0
+16383
Proportional Counts
±
10 V
-10.25 V
+10.25 V
-32768
+32767
0–10 V
-0.50 V
+10.25 V
-32768
+32767
0–5 V
-0.50 V
+5.50 V
-32768
+32767
1–5 V
+0.50 V
+5.50 V
-32768
+32767
0–20 mA
0.0 mA
+20.5 mA
-32768
+32767
4–20 mA
+3.5 mA
+20.5 mA
-32768
+32767
1746-NI4-
±
10 V
-10 V
+10 V
-32768
+32767
compatible
➀
0–10 V
0 V
+10 V
0
+32767
0–5 V
0 V
+5 V
0
+16384
1–5 V
+1 V
+5 V
+3277
+16384
0–20 mA
0 mA
+20 mA
0
+16384
4–20 mA
+4 mA
+20 mA
+3277
+16384
User-defined
±
10 V
-10.25 V
+10.25 V
scale A (and B)
0–10 V
-0.50 V
+10.25 V
0–5 V
-0.50 V
+5.50 V
See note
➁
.
1–5 V
+0.50 V
+5.50 V
0–20 mA
0.0 mA
+20.5 mA
4–20 mA
+3.5 mA
+20.5 mA
➀
Provides direct compatibility with the 1746-NI4 module.
➁
For user-defined scale A (or B ), the data in output words 4 and 5 (or 6 and 7) determine
the count limits. See the next subsection,
Setting The User-Defined Scale Limits, for
information on the User-Defined Scale data format .
➂
Note: Modules marked Series B Revision 1.00 or earlier had different signal limits for the
Scaled for PID data format (see the Owner’s Guide that came with your module).