3-10
Flex™ IO Isolated RTD/Thermocouple Module
User's Manual Pub. 0300242‐01 Rev. A
Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Range:
0 0 1 0 0 K
Type
Thermocouple
0 0 1 0 1 N
Type
Thermocouple
0 0 1 1 0 R
Type
Thermocouple
0 0 1 1 1 S
Type
Thermocouple
0 1 0 0 0 T
Type
Thermocouple
0 1 0 0 1 100
Ω Pt α 0.385
0 1 0 1 0 200
Ω Pt α 0.385
0 1 0 1 1 500
Ω Pt α 0.385
0 1 1 0 0 1000
Ω Pt α 0.385
0 1 1 0 1 100
Ω Pt α 0.3916
0 1 1 1 0 200
Ω Pt α 0.3916
0 1 1 1 1 500
Ω Pt α 0.3916
1 0 0 0 0 1000
Ω Pt α 0.3916
1 0 0 0 1 10
Ω Cu α 0.426
1 0 0 1 0 100
Ω Ni α 0.618
1 0 0 1 1 120
Ω Ni α 0.672
1 0 1 0 0 604
Ω NiFe α 0.518
1 0 1 0 1 R
0
to
150
Ω
1 0 1 1 0 R
0
to
1000
Ω
1 0 1 1 1 R
0
to
3000
Ω
1 1 0 0 0 +/-
50
mV
1 1 0 0 1 +/-
100
mV
3.4.3 Input Filter [Words 1 – 8 (Bits 5 to 7)
Use the table below to select the appropriate filter for each channel.
Table 3-4 (Filter Settings)
Bit 7 Bit 6 Bit 5 ADC Filter:
0 0 0 4.17
Hz
0 0 1 10.0
Hz
0 1 0 16.7
Hz
0 1 1 19.6
Hz
1 0 0 62.0
Hz
1 0 1 470.0
Hz
1 1 0 *Unused
1 1 1 *Unused
3.4.4 Data Format [Words 1 – 8 (Bits 8 to 10)
Select the appropriate data type for each channel using the table below. Refer to Table
3-6 for data type ranges.