beautypg.com

Spectrum Controls 1794sc-IRT8I User Manual

Page 35

background image

Chapter 3: Configuring the 1794sc-IRT8I for ControlLogix/CompactLogix

3-9

User's Manual Pub. 0300242‐01 Rev. A

Usage (16 bit words):

15

14

13 12 11

10 9 8 7 6 5 4 3 2 1 0

C:7 Temp

Units

Ch6

Disable

CJC
Ch6

Open

Circuit

Ch6

R

1

Data

Format

Ch6

Input
Filter

Ch6

Input

Type

CH6

C:8 Temp

Units

Ch7

Disable

CJC
Ch7

Open

Circuit

Ch7

R

1

Data

Format

Ch7

Input
Filter

Ch7

Input

Type

CH7

C:9 CH0 User Low Alarm Threshold
C:10 CH0 User High Alarm Threshold
C:11 CH0 User Alarm Deadband
C:12 CH1 User Low Alarm Threshold
C:13 CH1 User High Alarm Threshold
C:14 CH1 User Alarm Deadband
C:15 CH2 User Low Alarm Threshold
C:16 CH2 User High Alarm Threshold
C:17 CH2 User Alarm Deadband
C:18 CH3 User Low Alarm Threshold
C:19 CH3 User High Alarm Threshold
C:20 CH3 User Alarm Deadband
C:21 CH4 User Low Alarm Threshold
C:22 CH4 User High Alarm Threshold
C:23 CH4 User Alarm Deadband
C:24 CH5 User Low Alarm Threshold
C:25 CH5 User High Alarm Threshold
C:26 CH5 User Alarm Deadband
C:27 CH6 User Low Alarm Threshold
C:28 CH6 User High Alarm Threshold
C:29 CH6 User Alarm Deadband
C:30 CH7 User Low Alarm Threshold
C:31 CH7 User High Alarm Threshold
C:32 CH7 User Alarm Deadband

1

Reserved set to zero

3.4.1 Fault Mode [Word 0 (Bits 2,3,4,5,10,11,12,13)]

The fault mode bits are used to enable or disable “broken wire detection”. See table
below.

Table 3-2 (Fault Mode)
State Function
0 Disabled
1

Enable Broken Wire Detection

3.4.2 Input Type [Words 1 – 8 (Bits 0 to 4)]

Use the table below to select the input type for each channel.

Table 3-3 (Input Type)
Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Range:
0 0 0 0 0 B

Type

Thermocouple

0 0 0 0 1 C

Type

Thermocouple

0 0 0 1 0 E

Type

Thermocouple

0 0 0 1 1 J

Type