beautypg.com

Spectrum Controls 1762sc-OF8 User Manual

Page 23

background image

Chapter 3: Configuring the 1762sc-OF8 for RSLogix 500

3-3

User’s Manual Pub. 0300246-01 Rev. B

5.) Repeat steps 1 through 4 for additional modules.

Section 3.4
Module
Configuration

The OF8 module is configured using a process that employs the input and output files.
The following flow chart describes the configuration process.

Note: Each command issued will have a corresponding module response
in the input data file. See Section 3.5.1 for more information.

Note: For proper operation, during the 600 ms delay, the output words
should be set to the correct command values to avoid sending erroneous
analog signals.

Transition

To

Run

Unlock

Command

Issued

Write

Configuration

Data

Issue Load

Configuration

Command

Issue

Exit

Command

600 ms

Delay

Module

Enters Run

Mode