beautypg.com

Spectrum Controls 1762sc-OF8 User Manual

Page 14

background image

2-4

MicroLogix™ 1200 IO 8 Ch Output Module



User’s Manual Pub. 0300246-01 Rev. B

2.4.1 Minimum Spacing

Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50.8
mm (2 in.) of space on all sides for adequate ventilation, as shown:
Figure 2-1

Note: 1762 expansion I/O may be mounted horizontally only.

!

Attention

During panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the module.
Debris that falls into the module could cause damage when power is
applied to the module.

2.4.2 DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022 - 35
x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).

Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN rail
mounting area of the module against the DIN rail. The latch will momentarily open and
lock into place.

Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35) for
environments with vibration or shock concerns.