beautypg.com

2-4 terminal definitions, 2-5 wiring notices – OPTI-UPS DS200KC33II User Manual

Page 23

background image

4-2-4 Terminal Definitions

(1) I/R : Rectifier Input R Phase
(2) I/S : Rectifier Input S Phase
(3) I/T : Rectifier Input T Phase
(4) I/N : Input Neutral Line
(5) I2/R : Slave UPS Input R Phase (from slave UPS input R phase for paralleling system)
(6) I2/S : Slave UPS Input S Phase (from slave UPS input S phase for paralleling system)
(7) I2/T : Slave UPS Input T Phase (from slave UPS input T phase for paralleling system)
(8) BP/R : Bypass Input R Phase
(9) BP/S : Bypass Input S Phase
(10) BP/T : Bypass Input T Phase
(11) BP/N : Bypass Input Neutral Line
(12) O/N : Output Neutral Line
(13) O/R : Output R Phase
(14) O/S : Output S Phase
(15) O/T : Output T Phase
(16) B+ : Battery Input Anode
(17) G : Grounding
(18) B- : Battery Input Cathode

4-2-5 Wiring Notices

Battery

(1) For safety, professional engineers should put on isolated gloves, use tools with isolated handles. It is

recommended that two or more engineers are working on wiring the batteries.

(2) Check if batteries are well grounded and make sure your limbs are dry before you perform battery

disconnection.

(3) Disconnect UPS and batteries (switch off the battery breaker and unplug the battery connector) and

then disconnect cables of batteries on every layer.

(4) During battery disconnection, do not touch neighboring batteries while processing cables or plates of

batteries in order not to cause short circuit.

(5) During battery connection, finish connecting batteries on each layer firstly and then interconnect the

battery layers. Finally connect the battery connector to the battery breaker.

(6) Check terminal voltage and polarity of the batteries and the UPS battery input.

Check the following items after wiring setup:

(1) Every terminal is correctly connected.
(2) PE cable is correctly grounded.
(3) Every screw is tightly screwed.
(4) All switches should stay off (at off position).
(5) Output power distribution panel is not short circuited.
(6) Battery terminals and polarities are correctly connected.