Specifications

HI 9935

RANGE

0.00 to 14.00 pH and 0.00 to 1999 ppm (mg/L)

RESOLUTION

0.01 pH and 1 ppm (mg/L)

ACCURACY

±0.02 pH and ±2% F. S.

(@20°C/68°F)
TYPICAL EMC

±0.1 pH and ±2% F. S.

DEVIATION
CALIBRATION

WEIGHT

1.6 Kg (3.5 lb.)

ENCLOSURE

181 x 221 x 142mm (7.1 x 8.7 x 5.6")

CASE MATERIAL

Fiber-reinforced, self-extinguishing ABS

SETPOINT RANGE

From 4.0 to 7.0 pH and 900 to 1800 ppm (mg/L)

PROPORTIONAL
CONTROL

ALARM
CONTACT

POWER SUPPLY 220/240V or 110/115V at 50/60Hz

DOSING
TERMINALS

ENVIRONMENT

-10 to 50°C (14 to 122°F)

max. 95% RH non-condensing

Through "OFFSET" and "SLOPE" trimmers for pH, and
“ZERO CAL” and “SLOPE CAL” for TDS

Two independent controls: pH from 0.0 to 2.0 and
TDS from 0.0 to 400 ppm (mg/L) with two separate
time cycles from 0 to 90 seconds

Terminals can be configured as normally open or
normally closed (isolated output Max. 2A, Max. 240V,
resistive load, 1,000,000 strokes). The alarm is
activated if pH falls below the setpoint by the user-
selectable interval (0 to 2 pH),or TDS exceeds the
setpoint by more than the user-selectable interval (0
to 400 ppm) or due to overdosage

TDS RATIO

0.65 ppm (mg/L) = 1 µS/cm

Two sets of independent terminals (115 to 240V, Max.
2A, 1,000,000 strokes) are activated whenever pH
exceeds the pH setpoint and for the TDS falls below
the TDS setpoint

PROBE

Any combination pH electrode with a universal BNC
connector and Hanna TDS 4-ring potentiometric probe
with built-in temperature sensor and DIN connector
(optional)

GENERAL POINTS

• The relay terminals

relay terminals

relay terminals

relay terminals

relay terminals of the controller are powered

powered

powered

powered

powered. This

means that you can simply hook up your pump or electrovalve
directly to the controller and do not need additional power
supply.