Ontrol – Hall Research HR-4P User Manual
Page 10
Model HR-4P Programmer
10
Figure 9
– Output
Pulse
If any of the units I/O is configured as an output, you can pulse that output one or more times based on a specific
input condition. The Pulse Width and Delay between Pulses is selectable in milliseconds. The delay is only
required when more than one pulse is being sent.
Select the Pulse from the Action drop-down menu and pick a desired output channel, the Number of Pulses and
the Pulse Width.
When done, the user clicks the Add button to append the command as shown in Figure 10.
Figure 10
– Pulse
I/O Control
The I/O Control tab allows the user to configure any or all four discrete I/O‟s as inputs or outputs.
An input can be defined as Input-Contact or Input-Voltage. When an input is defined as “contact” you can just use
a contact closure or switch to ground with no additional circuitry, or use a digital signal that swings anywhere from 0
to 24v. In this mode the input of HR-4P is high impedance (>50 KOhm). When an input is defined as “voltage” then
the HR-4P will terminate the input with a 1K ohm resistor to ground. In this mode it will not be able to sense a
contact to ground (since the pull-down resistor is already keeping the pin at ground potential), but it is useful for
sensing DC supplies that can be a DC voltage from 3 to 24 vDC.
A good example is if you want to detect 110 VAC. In that case you can simply use a small 6v DC power adapter
and plug it into the AC line, and tie the 6v DC to the HR-4P. When configured as Voltage input, the 1K resistor will
bleed off and decay the DC signal from the external supply when the AC voltage is disconnected.