16 routine cleaning and inspection – Glow-worm Xtrafast 96-120 User Manual
Page 25

25
2000221595
16 Routine Cleaning and Inspection
SPARK GAP
SENSE GAP
9877
Diagram 16.6
9876
Diagram 16.7
9875
FLOW
RESTRICTOR
AND COLD
WATER INLET
FILTER
16.10 Spark and Sense Gaps
• Check that the spark and sense gaps as shown in diagram
16.6.
16.11 Flue system
• Check externally to make sure that flue is not blocked
• Inspect flue system to make sure that all fittings are secure.
16.12 Operation of fan
• Switch on electrical supply and turn on gas.
• Light burner by opening a hot water tap.
• Check that fan operates when burner lights and stops when it
goes out.
16.13 Cold water inlet filter
Drain down domestic hot water circuit of boiler only, as follows:
• Close isolating valve/throttle (m) on cold water isolating cock,
see diagram 7.1.
Note: This valve is closed when screwed fully clockwise.
• Undo connecting nut from boiler cold water inlet connection.
• Clean and inspect filter, replace if necessary, see diagram
16.7.
• With both filter and restrictor in place, reconnect connecting
pipe to inlet connection and tighten.
• Fully open isolating valve/throttle on cold water inlet and check
for leaks.
4mm
4mm
5mm