18.8.1

Spark electrode

• Disconnect the electrode inlet (3) and the grounding cable (2).

• Remove the 2 spark electrode retaining screws (4).

• Carefully remove the electrode from the combustion

chamber.

• Check that the extremes of the electrode (6) are not

damaged.

• Clean away any accumulation of dirt and check that the

distance between the two electrodes is between 3.5 and 4.5

mm.

• Check that the gasket (5) is not damaged. Replace if

necessary.

18.8.2

Dismantling the burner

b

Warning: The gasket (12) must be replaced each

time the burner is dismantled.

• Disconnect the spark electrode connector (6) from the igniter

unit.

• Remove the gas pipe (17).

• Remove the connectors from the gas valve (1) and the fan

(15).

• Remove the retaining screw of the silencer.

• Loosen the 4 nuts (7).

• Remove the burner group from the heat exchanger (11).

• The studs (8) fixed to the heat exchanger must not

be damaged. Should it be damaged, replace the heat

exchanger.

• The burner gate insulation should not be damaged Replace

if damaged.

18.8.3

Cleaning the heat exchanger

• Clean the coil (19) in the heat exchanger (11) with water.

18.8.4

burner control

• The burner (13) does not require maintenance and should

not be cleaned.

• Check that its surface is not damage. Replace the burner if

necessary.

• Following the verification or replacement of the burner,

assemble the burner group as described in the following

chapter.

18.8.5

Re-assembling the burner group

• Place the burner group on the heat exchanger (11).

• Progressively tighten the 4 nuts (7) in an alternate order.

• Reassemble the silencer.

• Connect the gas tube (17) with a new gasket to the burner

group.

• Connect the spark electrode connector (6) to the igniter unit.

• Connect the connector to the gas valve (1) and the fan (15).

• Open the appliance gas input.

• Check the watertightness of the gas connection.

18.9 Service completion

• Re-check the combustion, see chapter "Combustion check".

On completion of the service, the "Benchmark" Service Record

sould be completed.

MAINTENANCE