beautypg.com

Installation, 13 specific adjustment – Glow-worm Ultracom2 sxi User Manual

Page 28

background image

0020092785_02 - 05/10 - Glow-worm

- 26 -

12.6 Testing heating system

• Ensure that the external controls and programmer are calling

for heat.

• Fully open all radiator valves, see chapter "Appliance

installation

Recommendations before installing Heating

circuit design".

• Activate the C.H. function on the appliance's control panel.

• Balance the radiators as required to give the required system

differential.

• Turn off all radiators that can be shut off by the user and

check to see if less than the maximum differential allowed of

20°C can be achieved across flow and return.

i

Should the appliance require adjustment refer to

specific adjustment section overleaf.

• Allow the system to reach maximum temperature then switch

off the boiler by isolating from the electrical supply.

• Drain the entire system rapidly whilst hot, using the drain

taps at all the low points of the system. Fill and vent the

system as described previously in chapter "Commissioning

► Filling the CH system (Central heating)".

• Adjust the boiler temperature controls and any system

controls to their required settings.

12.7 Testing domestic hot water system

• Check that the temperature obtained is compliant with the

setting on the appliance (Smart wiring centre only).

12.8 Completion

• Ensure that the magnetic lighting instruction label is placed

on the surface of the boiler casing.

GB: It is a requirement that the “Benchmark” Installation,

Commissioning and Service Record is completed and left with

the user.

IE: it is necessary to complete a “Declaration of Conformity” to

indicate compliance to I.S.813. An example of this is given in

the current edition of I.S.813.

13 Specific adjustment

13.1 Heating circuit adjustment

It may be necessary to adjust the by-pass to the design of the

system. The boiler is delivered pre-set open 1/2 turn (1).

1

Key

1 Screw for by-pass

• Depending on the design of the system the by-pass may

need further adjustment. It is adjusted clockwise to close and

anti-clockwise to open. This should be balanced to ensure

that it operates if the pump output is adjusted.

Output/pressure curve Ultracom

2

12sxi / 18 sxi

60
50
40
30
20
10

0

500

1000

1500

B

1

2

3

4

Key

A Available pressure between heating flow and return (kPa)

B Heating circuit flow rate (l/h)

1 Speed min, bypass closed

2 Speed max, bypass closed

3 Speed max, bypass middle position

4 Speed max, bypass opened

Output/pressure curve Ultracom

2

30sxi

60
50
40
30
20
10

0

500

1000

1500

B

1

2

3

4

Key

A Available pressure between heating flow and return (kPa)

B Heating circuit flow rate (l/h)

1 Speed min, bypass closed

2 Speed max, bypass closed

3 Speed max, bypass middle position

4 Speed max, bypass opened

INSTALLATION