beautypg.com

Installation – Glow-worm Clearly Solar Cylinders User Manual

Page 18

background image

0020115479_03 - 10/12 - Glow-worm

- 16 -

INSTALLATION

9.3.2

Discharge requirements (g3 building

regulations)

METAL DISCHARGE PIPE FROM

TEMPERATURE RELIEF VALVE

TO TUNDISH

METAL DISCHARGE PIPE

FROM TUNDISH WITH

CONTINUOUS FALL

TUNDISH

DISCHARGE

BELOW

FIXED

GRATING

FIXED

GRATING

TRAPPED GULLY

SAFETY DEVICE

(E.G. TEMPERATURE

RELIEF VALVE

VENTIL)

600 MM

300 MM

MINIMUM

The discharge connections of the temperature/pressure relief

valve and the expansion relief valve must be connected with

the supplied tundish via 15 mm copper piping. The tundish

should be attached so that it is vertical, as near to the cylinder

as possible, and not more than 600 mm from the connection

of the temperature/ pressure relief valve. It must be mounted

in the same room as the cylinder at a sufficient distance from

the electrical components. The discharge pipes from the

temperature/pressure relief valve and expansion relief valve can

be joined above the tundish using a T-piece.

The discharge pipe from the 22 mm connection of the drain

funnel must be laid using copper piping with a diameter of at

least 22 mm to a safe and visible discharge point.

There must be a vertical section of pipe at least 300 mm long

beneath the tundish before any bends or elbows in the pipework.

If the total resistance of the discharge pipe exceeds the values

specified in table below, you must increase the diameter of the

piping. When installing the discharge piping, you must observe

Directive G3 (section 2.5).

9.3.3

sizing of copper discharge pipe for g1/2

temperature and pressure relief valve outlet size

Minimum diameter of

discharge pipe from

tundish

Maximum

permissable total

resistance, expressed

as straight pipe

length (without

elbows or bends)

Resistance due to

each elbow or bend

22 mm

Up to 9 m

0.8 m

28 mm

Up to 18 m

1.0 m

35 mm

Up to 27 m

1.4 m

Worked example

The example below is for a G1/2 temperature relief valve with

a discharge pipe having 4 No. 22 mm elbows and length of 7 m

from the tundish to the point of discharge.

From Sizing Table:

Maximum resistance allowed for a straight length of 22 mm

copper discharge pipe from a G1/2 temperature relief valve is:

9.0 m.

Subtract the resistance for 4 No. 22 mm elbows at 0.8 m each =

3.2 m.

Therefore the maximum permitted length equates to: 5.8 m,

which is less than the actual length of 7 m therefore calculate the

next largest size.

Maximum resistance allowed for a straight length of 28 mm pipe

from a G1/2 temperature relief valve is: 18 m.

Subtract the resistance of 4 No. 28 mm elbows at 1.0 m each =

4.0 m.

Therefore the maximum permitted length equates to: 14 m.

As the actual length is 7 m, a 28 mm copper pipe will be

satisfactory.

A suitable place for the end of the discharge pipe is, for

example, beneath a fixed grille above the odour seal in a gully

with a siphon. Low discharge pipes, for example up to 100 mm

above external surfaces such as car and other parking spaces,

grasslands etc. can be used provided that they are secured by a

wire fence or something similar to prevent children from coming

into contact with the waste water and as long as the system is

not visible. You must not install any valves or stop cocks in the

discharge pipe.

• Make sure that the discharge pipe from the tundish to the

drain has a constant downward incline of at least 1:200. The

discharge pipe from the pressure relief valve of the Glow-worm

gas-fired boiler can be connected to the horizontal discharge

pipe of the cylinder behind the tundish using a T-piece.