5 commissioning – Glow-worm Clearly Solar System User Manual

Page 21

background image

21

Display

Turn the dial to adjust

Setting range

Factory setting

Not used.

20 - 90 °C

60 °C

Not used.

5 – 12 K

7 K

Not used.

1 – 10 K

3 K

PRIO

Cylinder with highest priority

1, 2

1

AGEL:

Frost protection function

-5

o

C – 10

o

C; OFF

OFF

PROT

Solar circuit safeguard

OFF, 110

o

C – 150

o

C

130

o

C

CST:

Collector type

1 = Flat collector

2 = Tubular collector

1, 2

1

LEG

Anti-Legionella function

OFF, 1, 2, 3, 4, 5, 6, 7, 1-7

OFF

LEGT:

Start time for the anti-Legionella function

00:00 - 23:50

04:00

5 Commissioning

Table 1 System parameters (continued)