Technical data, 5 envirosorb 5 – Glow-worm Clearly Heat Pump 5 kW User Manual
Page 11

0020111744_00 - 09/10 - Glow-worm
- 9 -
TECHNICAL DATA
TECHNICAL DATA
5 Envirosorb
5
Description
Unit
Envirosorb
5
Min. operational range (in heating)
°C
-7
Max. operational range (in heating)
°C
35
Specifi cations, with radiators
(fl ow : 45°C, return : 40°C, outside dry temperature (wet) 7 (6)°C)
Heating output
kW
4.41
Power input
kW
1.46
Rated electrical current
A
6.34
COP* A7(6) W45-40
3.02
Specifi cations, with fl oor heating
(fl ow : 35°C, return : 30°C, outside dry temperature (wet) : 7 (6)°C)
Heating output
kW
4.70
Power input
kW
1.26
Rated electrical current
A
5.48
COP* A7(6) W35-30
3.73
Refrigerant circuit
Type of refrigerant
R-410A
Quantity of refrigerant
kg
1.8
Type of compressor
Rotary
Type of oil
Polyolester
Type of regulator
Electronic
Fan speed
rpm
180 - 660
Maximum operating pressure (PS) in low
pressure
bar
34
Pa
34 x 10
5
Maximum operating pressure (PS) in high
pressure
bar
43.2
Pa
43.2 x 10
5
Heat pump circuit
Min. supply pressure
bar
1
Pa
1 x 10
5
Max. supply pressure.
bar
3
Pa
3 x 10
5
Minimum static pressure
bar
1
Pa
1 x 10
5
Nominal water fl ow rate in heating mode
l/h
800
Minimum water fl ow rate
l/h
500
Minimum recommended water fl ow
l/h
750
Maximum recommended water fl ow
l/h
850
Minimum outlet temperature setting
(in heating)
°C
25
Maximum outlet temperature setting
(in heating)
°C
55
Heat pump water volume
l
1
Description
Unit
Envirosorb
5
Electrical
Supply voltage/frequency
V/Hz
1/N/PE
230V 50Hz
Fuse (x2)
T2A / 250V
Maximum absorbed power (P max)
kW
1.45
Real power absorbed by the fan and pump
(with heating resistors)
kW
1.48
Real power absorbed by the fan and pump
(without heating resistors)
kW
1.35
Maximum absorbed current (I max)
A
6.70
Real current absorbed by the fan and pump
(with heating resistors)
A
6.43
Real current absorbed by the fan and pump
(without heating resistors)
A
5.88
Starting current (with start-up current limiter)
A
< 20
Index of electrical protection
IPX4
Electrical classifi cation
I
Surge category
II
Pollution rating
2
Description
Unit
Envirosorb
5
Dimensions
Height
mm
935
Width
mm
880
Depth
mm
345
Ø Water circuit connections
"
1
Nett total weight
kg
82.5
Sound power level : overall exterior noise
(according to EN 12102 and EN ISO 9614-1)
dBA
62.6
* Coeffi cient Of Performance (according to EN 14511)
** Energy Effi ciency Ratio (according to EN 14511)
i
Fluorinated greenhouse gases as identifi ed in
the Kyoto protocol, are contained within a fully
sealed system.