Example for creating a device class file, Examine source files – Echelon LonBridg Server User Manual
Page 50

44
LonBridge Device Class File
2. Define an
application requires.
3. Decide which network variables or fields within network variables the
LonBridge application needs to access. The application can include a
subset of the network variables or network variable fields that are
defined for the L
ON
W
ORKS
device. Recommendation: If you define a
subset, include any mandatory network variables.
4. Define an
variable fields that correspond to each
variables are defined within the L
ON
W
ORKS
device’s source files.
5. Use the NodeBuilder Resource Editor to determine the definitional
attributes of each network variable or field, such as its number of bytes,
type values, or enumeration values. You can also use the LONMARK
Resource Files Web page,
, to determine this
information.
6. Optional: Define
element (inside the
variable or field values.
7. Browse the L
ON
W
ORKS
device’s external device interface (XIF) file to
determine the index value for each network variable. These index values
are required for each
Example for Creating a Device Class File
The following sections describe how to create a device class file for a simplified
Lamp Module, based on the Echelon Lamp Module. The example LonBridge
application for this simplified Lamp Module requires attributes for lamp state (on
or off) and for lamp power use.
Examine Source Files
For the Echelon Lamp Module, all network variable declarations are included in
a common header file that defines network variables, configuration properties,
functional blocks, and other Neuron C constructs (such as global variables,
functions, ISI callback functions, and so on).
The header file defines the following network variables. Note that the file defines
more network variables than the simplified Lamp Module will need.
///// Network Variables /////
network input SNVT_switch_2 nviValue;
network input SCPTenergyCntInit cp cpMinSendTime = 5;
// Set default throttle to 500ms
network output polled SNVT_switch_2 nvoValueFb
nv_properties {
cpMinSendTime
};
network output SNVT_occupancy nvoOccupancyFb;
network input far SCPTpwrSendOnDelta cp cpPwrSendOnDelta = 5;