CPD 3000 Integration Guide
23
E
WARMUP state timer expires OR commanded OFF
Updates to nviLampValue are
delayed until out of WARMUP.
F
COOLDOWN state timer expires AND (.defaultLev > 0
AND rcvTmo) OR command ON
Occurs when .warmupTm is > 0
G
WARMUP state timer expires AND (commanded ON
OR (rcvTmo AND .defaultLev > 0))
H
command OFF OR (rcvTmo AND .defaultLev == 0)
COOLDOWN for at least 10 for
inrush circuit recovery
I
.warmupTm == 0 AND (Command ON OR (rcvTmo
AND .defaultLev > 0)
During the transition from OFF to ON, the CPD 3000 drives the 0-10V control
signal directly to the final level at the time the load switching relay is engaged. If
the CPD 3000 is configured with a nciControlCfg.warmupTm > 0, the control
signal is driven to the 100% level, and finally the level defined by
nviLampValue.value
after the warmupTm has completed. Changes in lamp level
while the load is ON are applied as a smooth ramp over the time specified by
nciControlCfg.rampTm
(0 – 30.0 s, 0.1s steps). The transition to OFF will sweep
the 0-10V control to the minimum level before releasing the load switching relay.
Creating the CPD 3000 Device on your SmartServer
To create a L
ON
W
ORKS
device, follow these steps. For more information, see
Creating LonWorks Devices in Chapter 5 of the SmartServer User’s Guide.
If you are using the SmartServer in Standalone mode, copy the following files to
the SmartServer flash disk:
• Copy the external interface (XIF) files of the devices to be managed by the
SmartServer to the root/LonWorks/import folder on the SmartServer flash
disk.
• Copy the device resource files to the root/LonWorks/types/user folder.
• If you plan on upgrading the devices using the SmartServer, you need to copy
the devices’ application image files to the root/LonWorks/import folder.
• Reboot the SmartServer.