Echelon Lumewave CPD 3000 Lighting Controller User Manual
Page 16
![background image](/manuals/735714/16/background.png)
16
CoolDownTm
will extend this time.as
required when controlling certain lamp
types such as HPS.
rampTm SNVT_time_sec
Controls how the LC ramps between level
transitions. Only used after the lamp is
ON to go between intermediate steps. The
CPD 3000 limits this value to a maximum
of 30s. (Default value – 1.5s)
supplyVoltage SNVT_volt
The nominal supply voltage for the fixture.
Used of voltage level alarms. (Default
value – 240V).
warmupTm unsigned
short
The number of minutes the LC allows the
fixture to warm up before allowing
dimming commands. During warm up, the
dimming commands are deferred. If the
LC is set to go to 75% ON, the LC will set
the 0-10V signal to 10V for warmupTm
minutes before issuing the appropriate
dimming level. In LED applications, this
is typically 0. Any nviLampValue less
than 100% will be delayed while the LC is
in the state OLC_WARMUP. (Default value –
0s). This also delays power alarm
processing which is important in the case
of control of magnetic ballast technology.
coolDownTm unsigned
short
The number of minutes the LC will delay
commands to turn ON after the fixture has
been turned OFF. This is important for
improving certain lamp technology life
times. The CPD 3000 enforces a 10s
COOLDOWN to allow recovery of the
inrush protection circuit. This 10s
minimum is subject to change in the
future. (Default value – 0s)
maxRcvTm SNVT_time_sec
If the LC fails to receive an update to
nviLampValue
for this time (0s default),
the LC will drive the lamp to the
defaultLevel
. The segment controller
should update nviLampValue up to three
times within this period. If the maxRcvTm
is 900s, the heartbeat rate of 300s should
be used by the segment controller. Note
that maxRcvTm = 0 means lights will
retain the last commanded value if the
SmartServer cannot communicate to the
device, or if it fails.
minPWM unsigned
long
It may be necessary to set the lowest 0-
10V signal to a value that can be used to
drive the controlled fixture. This value