Echelon Lumewave CPD 3000 Lighting Controller User Manual
Page 19
![background image](/manuals/735714/19/background.png)
CPD 3000 Integration Guide
19
controlled to defaultLev
(Default –0s; which means
HB checking is disabled)
nciPowerProfile UNVTpowerProfile
Defines the nominal power
at 0.5, 25, 50, 75, 100%
lamp
nviLampValue.value
.
Used to determine the
expected power draw using
linear interpolation for
nviLampValue.values
in
between steps defined in
the table.
nciLimits.powerLowFault SNVT_lev_cont
The percentage deviation
of expected power below
which the LowPower alarm
is triggered. (Default value
- 15%)
nciLimits.powerHighFault SNVT_lev_cont
The percentage deviation
of expected power above
which a HighPower alarm
is triggered. (Default
value - 15%).
nciLimits.voltageLow SNVT_lev_cont
The percentage deviation
below the configure
supplyVoltage
at which
the LowSupplyVoltage
alarm is triggered.
(Default value - 15%).
nciLimits.voltageHigh SNVT_lev_cont
The percentage deviation
above the configured
supplyVoltage
at which
the HighSupplyVoltag
alarm is triggered.
(Default value - 15%).
nciLimits.pfLow SNVT_pwr_fact
Power factor alarm point.
Power factor alarms are
only tested when the
controlled load is ON.
(Default value - .65)
nciLimits.rcvHb SNVT_time_sec
The rate at which the
segment controller is
expected to update
nviLampValue
. Best
practice is to set this value
at 3x shorter than
nciControlCfg.rcvTmo
(Default value – 0s).
nciLimits.highTemp SNVT_temp_p
The temperature above
which a high temperature