e. Adjust running and idle current
d. Set rotary switch for the motor selected
(This is normally set by the factory for the motor specified.)
Switch 1 and 2 set the running
current to 70%, 80%, 90%
or 100% of the motor’s
rated maximum current.
1 2
100%
1 2
90%
1 2
80%
1 2
70%
4
50%
4
90%
Switch 4 sets the idle current
to either 50% or 90% of the
selected running current.
Factory default is 90%.
OLE
Bimba Motor
Frame
Option Code
Setting
-75
17 frame
P1, E1, Y1, Z1
5
-75
23 frame
P2, E2, Y2, Z2
7
-150
23 frame
P2, E2, Y2, Z2
6
-350
34 frame
P3, E3, Y3, Z3
F
• Use 100% position in most ap-
plications (factory default)
• Use lower settings for self lock-
ing threads (OLE 12, 16, and
20 leads).
• Use lower settings to reduce
motor temperature
• Use higher settings for full hold-
ing torque
Turn the rotary switch to the number that represents
the motor you have. This sets current and anti-
resonance settings for optimum performance.
8
!
• Use lower setting during
initial setup to avert
accidental damage
• Use lower settings to address
safety issues
• Use lower settings to reduce
motor temperature