beautypg.com

Figure 4.4.8 mode 8 operation – ADLINK PXI-2502 User Manual

Page 49

background image

Operation Theorem

• 41

4.4.2.7 Mode7: Single Triggered Continuous Pulse Generation

This mode is similar to mode 5, except that the counter generates con-
tinuous periodic pulses with programmable pulse interval and pulse-width
following the first active edge of GPTC_GATE. Once the first
GPTC_GATE edge triggers the counter, GPTC_GATE takes no effect until
the software start is re-executed. Figure 4.4.7 illustrates the generation of
two pulses with pulse delay of four and pulse-width of three.

4

4

4

3

2

1

0

2

1

S o f t w a r e s t a r t

0

3

2

1

0

2

1

0

3

2

G a t e

C L K

C o u n t v a l u e

O U T

Figure 4.4.7 Mode 7 Operation

4.4.2.8 Mode8: Continuous Gated Pulse Generation

This mode generates periodic pulses with programmable pulse interval
and pulse-width following the software start. GPTC_GATE is used to
enable/disable counting. When GPTC_GATE is inactive, the counter halts
the current count value. Figure 4.4.8 illustrates the generation of two
pulses with pulse delay of four and pulse-width of three.

4

4

3

3

2

1

0

2

1

S o f t w a r e s t a r t

0

3

2

1

0

2

1

1

0

3

G a t e

C L K

C o u n t v a l u e

O U T

Figure 4.4.8 Mode 8 Operation

This manual is related to the following products: