beautypg.com

Delta Electronics Network Device none User Manual

Page 2

background image

Set Value

Alarm Type

Alarm Output Operation

4

Reverse deviation upper- and lower-limit:
This alarm output operates when PV value is in the range of the setting value SV+(AL-H)
and the setting value SV-(AL-L).

ON

OFF

SV

SV-(AL-L)

SV+(AL-H)

5

Absolute value upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value AL-H or lower
than the setting value AL-L.

ON

OFF

AL-L

AL-H

6

Absolute value upper-limit:
This alarm output operates when PV value is higher than the setting value AL-H.

ON

OFF

AL-H

7

Absolute value lower-limit:
This alarm output operates when PV value is lower than the setting value AL-L.

ON

OFF

AL-L

8

Deviation upper- and lower-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and the value is
higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L).

ON

OFF

SV

SV-(AL-L)

SV+(AL-H)

9

Deviation upper-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and the reached
value is higher than the setting value SV+(AL-H).

SV+(AL-H)

ON

OFF

SV

10

Deviation lower-limit with standby sequence:
This alarm output operates when PV value reaches the set point (SV value) and the
reached value is lower than the setting value SV-(AL-L).

SV-(AL-L)

ON

OFF

SV

11

Hysteresis upper-limit alarm output:
This alarm output operates if PV value is higher than the setting value SV+(AL-H). This
alarm output is OFF when PV value is lower than the setting value SV+(AL-L).

ON

OFF

AL-L AL-H

12

Hysteresis lower-limit alarm output:
This alarm output operates if PV value is lower than the setting value SV-(AL-H). This
alarm output is OFF when PV value is higher than the setting value SV-(AL-L).

ON

OFF

AL-H AL-L

13

CT alarm output:
This alarm operates when the current measured by transformer (CT) is lower than AL-L or
higher than AL-H (This alarm output is available only for the controller with current
transformer).

ON

OFF

AL-L

SV

AL-H

14

When program control is end status, alarm output is ON.

15

When RAMP UP status happens to PID program control, alarm output is ON.

16

When RAMP DOWN status happens to PID program control, alarm output is ON.

17

When SOAK status happens to PID program control, alarm output is ON.

18

When RUN status happens to PID program control, alarm output is ON.

Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L

 

Current Transformer (CT) Function

The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with the
controller, change the corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn to operation
mode and set the current lower-limit and current upper-limit. You can set current alarm range between 0.5A ~ 30A, display
resolution is 0.1A and measure accuracy is +/- 0.5A.

 

EVENT Inputs Function

There are two optional event inputs (contact inputs) supported (EVENT1and EVENT2) in DTB series.
EVENT1 : RUN/STOP operation can be executed by RUN/STOP parameters (Operation Mode) or via the communication.
User also can control RUN/STOP operation by EVENT 1 in DTB series. The control output is ON if the circuit of EVENT 1
is open when the controller is operating. Otherwise, the controller will stop output if the circuit of EVENT 1 is short or when
the system parameter of the controller is set to STOP mode.
EVENT2 : DTB series allows user can switch two temperature setting value by changing the status (open/short) of EVENT
2. Each temperature setting value has independent control parameters.

 

PID Program Control (Ramp/Soak Program Control)

Description of Function and Parameters Setting:
PID program control by 8 patterns (Pattern No. 0~7) is supported in DTB series. Each pattern contains 8 steps (step No. 0
~ 7), one Link Pattern parameter, one Cycle parameter and one Actual Step parameter
Start Pattern :

is in operation mode and it is used to set the Start Pattern of PID program control (This parameter

appear in

mode only).

Steps : Include set point X and execution time T, these two parameters setting. The set point (SV) should reach
temperature X after the period of execution time T. If the set point is the same as the result of the previous setting, then it is
called Soak program control. If not, then it is called Ramp program control. Therefore, PID program control is also called
Ramp/Soak program control.
The default of step No. 0 in this controller is Soak program control. The controller will control the temperature (PV) to
reach the set point X and then keep the temperature at set point X. The period of execution time is time T which provided
by step No. 0.
Link Pattern Parameter : For example, when set

to 2, it indicates that pattern No. 2 will execute next after the

execution of pattern No. 0. If set to

, it indicates the program will stop after executing the current pattern and the

temperature will keep at the set point of the last step.
Cycle Parameter : Additional execution cycle number. For example, when set

to 2, it indicates that pattern No. 4

should execute twice in addition. Include origin one time execution, total execute three times.
Actual Step Parameter : Execution step number per pattern (can set to 0 ~ 7). For example, when set

to 2, it

indicates that pattern No 7 will not execute other steps than step 0 to step2.
Execution : When

is set to

, the program will start to execute in order from the step 0 of start pattern.

When

is set to

, the program will stop and the control output is disabled.

When

is set to

, the program will stop and the temperature at that time will be controlled at the set point

before program stop. Select

again, then the program will restart and execute from step 0 of start pattern.

When

is set to

, the program will hold and the temperature at that time will be controlled at the set point

before program hold. Select

again, then the program will follow the step before hold and start to execute through

the rest of the time.
Display : During PID program control, the SV default display is P-XX, P indicates the current execution pattern and XX
indicates the current execution step. Press

to change the display item.

After select

, press

key, and then the temperature set point of the current execution step will display on SV

display.
After select

, press

key, and then the residual time of the current execution step will display on SV display.

 

PID Control

One group can be selected from any one of 4 groups PID parameters (P, I, D, IOF) for PID control. After AT, PID value and
temperature setting will be stored in the selected one group.

~

: PIDn, n = 0 ~ 4 from which 0 ~ 3 correspond to each PID parameter.

: n = 4, auto PID parameter.

Program will automatically select a most useful PID parameter based on current temperature setting. Displayed SV values
correspond to

~

~

: Temperature setting corresponded to the selected PID parameter via user-defined or AT.

Valve Control:
When use valve control as output control, there are 2 Relay outputs for motor forward/reverse control, one (output 1) for
valve open the other (output 2) for valve close. The output volume is controlled by valve open/close and it can be set with
feedback function enabled or disabled. When feedback is disabled, output 1 will keep output while valve fully opens and
output 2 will keep output while valve fully closes. But if feedback is enabled, please follow the parameter setting for valve
control as follows:

: Time for valve from full close to full open.

: Dead Band setting of valve. The value of current valve output minus previous one must be greater than Dead Band

value; otherwise, valve will remain OFF.

: Signal feedback setting, ON for enabling feedback and OFF for disabling feedback.

When

set to ” 1”, it means signal feedback function is activated and will come up selections as follows:

a.

: Upper/Lower limit of valve feedback by auto-tuning.

must set to

for showing up this selection.

b.

: D/A value when value fully opens. Set

to be ”1” for auto setting or ”0” for manual setting.

c.

: D/A value when value fully closes. Set

to be ”1” for auto setting or “0” for manual setting.

Note: If feedback function setting is with problem, program will see the setting as feedback disabled.

 

RS-485 Communication

1. Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps
2. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2
3. Communication protocol: Modbus (ASCII or RTU)
4. Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read

the bits data (Max. 16 bits). 05H to write 1 (one) bit into register.

5. Address and Content of Data Register:

Address

Content

Explanation

Measuring unit is 0.1, updated one time in 0.4 second
The following reading value display indicates error occurs:
8002H : Initial process (Temperature value is not got yet)
8003H : Temperature sensor is not connected
8004H : Temperature sensor input error
8006H : Cannot get temperature value, ADC input error

1000H

Process value (PV)

8007H : Memory read/write error

1001H

Set point (SV)

Unit is 0.1,

o

C or

o

F

1002H

Upper-limit of temperature range

The data content should not be higher than the temperature range

1003H

Lower-limit of temperature range

The data content should not be lower than the temperature range

1004H

Input temperature sensor type

Please refer to the contents of the “Temperature Sensor Type and
Temperature Range” for detail

1005H

Control method

0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control

1006H

Heating/Cooling control selection

0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating

1007H

1st group of Heating/Cooling control cycle

0 ~ 99, 0:0.5 sec

1008H

2nd group of Heating/Cooling control cycle

0 ~ 99, 0:0.5 sec

1009H

PB Proportional band

0.1 ~ 999.9

100AH

Ti Integral time

0 ~ 9,999

100BH

Td Derivative time

0 ~ 9,999

100CH

Integration default

0 ~ 100%, unit is 0.1%

100DH

Proportional control offset error value, when Ti = 0 0 ~ 100%, unit is 0.1%

100EH

The setting of COEF when

Dual Loop output

control

are used

0.01 ~ 99.99

100FH

The setting of Dead band when

Dual Loop

output control

are used

-999 ~ 9,999

1010H

Hysteresis setting value of the 1st output group

0 ~ 9,999

1011H

Hysteresis setting value of the 2nd output group

0 ~ 9,999

1012H

Output value read and write of Output 1

Unit is 0.1%, write operation is valid under manual tuning mode only.

1013H

Output value read and write of Output 2

Unit is 0.1%, write operation is valid under manual tuning mode only.

1014H

Upper-limit regulation of analog linear output

1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output)

1015H

Lower-limit regulation of analog linear output

1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output)

1016H

Temperature regulation value

-999 ~ +999, unit: 0.1

1017H

Analog decimal setting

0 ~ 3

1018H

Time for valve from full open to full close

0.1 ~ 999.9

1019H

Dead Band setting of valve

0 ~ 100%; unit: 0.1%

101AH

Upper-limit of feedback signal set by valve

0 ~ 1,024

101BH

Lower-limit of feedback signal set by valve

0 ~ 1,024

101CH

PID parameter selection

0 ~ 4

101DH

SV value corresponded to PID value

Only valid within available range, unit: 0.1 scale

1020H

Alarm 1 type

Please refer to the contents of the “Alarm Outputs” for detail

1021H

Alarm 2 type

Please refer to the contents of the “Alarm Outputs” for detail

1022H

Alarm 3 type

Please refer to the contents of the “Alarm Outputs” for detail

1023H

System alarm setting

0 : None (default), 1~3 : Set Alarm 1 to Alarm 3

1024H

Upper-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1025H

Lower-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1026H

Upper-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1027H

Lower-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1028H

Upper-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

1029H

Lower-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

102AH

Read LED status

b0 : Alm3, b1: Alm2, b2: F, b3: ℃, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT

102BH

Read pushbutton status

b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push

102CH

Setting lock status

0 : Normal, 1 : All setting lock, 11 : Lock others than SV value

102DH

CT read value

Unit: 0.1A

102FH

Software version

V1.00 indicates 0x100

1030H

Start pattern number

0 ~ 7

1040H~

1047H

Actual step number setting inside the correspond
pattern

0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N

1050H~

1057H

Cycle number for repeating the execution of the
correspond pattern

0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times

1060H~

1067H

Link pattern number setting of the correspond
pattern

0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution
pattern number after executing the current pattern

2000H~

203FH

Pattern 0~7 temperature set point setting
Pattern 0 temperature is set to 2000H ~ 2007H

-999 ~ 9,999

2080H~

20BFH

Pattern 0~7 execution time setting
Pattern 0 time is set to 2080H~2087H

Time 0 ~ 900 (1 minute per scale)

6. Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit

clear)

0810H

Communication write-in selection

Communication write in disabled: 0 (default), Communication write in
enabled: 1

0811H

Temperature unit display selection

o

C/linear input (default): 1 ,

o

F : 0

0812H

Decimal point position selection

Except for the thermocouple B, S, R type, all the other thermocouple
type are valid. (0 or 1)

0813H

AT setting

OFF: 0 (default), ON : 1

0814H Control

RUN/STOP

setting

0: STOP, 1: RUN (default)

0815H

STOP setting for PID program control

0: RUN (default), 1: STOP

0816H

Temporarily STOP for PID program control

0: RUN (default), 1: Temporarily STOP

0817H

Valve feedback setting status

0: w/o feedback (default), 1: feedback function

0818H

Auto-tuning valve feedback status

0: Stop AT (default), 1: Start AT

7. Communication Transmission Format: Command Code:02:read N bits,05:write 1 bit,03:read N words,06:write 1 word.

 

Panel Cutout & Terminal Definitions

„

Panel Cutout (dimensions are in millimeter and inch)

„

Terminals Definitions

DTB4824

65.0 min.

(2.56)

4

0

.0

m

in

.

(1

.5

8

)

44.8

(1.76)

2

2

.0

(0

.8

7

)

+0.6

-0

+0.02

-0

+

0

.6

-0 +

0

.0

2

-0

mm
(in)

DTB4824

1

4

3

2

5

6

AC 100~240V

50/60 Hz 5VA

Tc

+

-

RTD

OUT 1

DATA-

DATA+

RS-485

7

9

8

10

11

12

V

!

+

+

-

-

OUT 2/

ALM

V

+

-

IN

+

-

L

N

DTB4848

65.0 min.

(2.56)

4

5

.0

(1

.7

7

)

45.0

(1.77)

6

0

.0

m

in

.

(2

.3

6

)

+0.6

-0

+0.02
-0

+

0

.6

-0 +

0

.0

2

-0

mm

(in)

DTB4848
(EVENT & CT selection)

DTB4848
(NO EVENT & CT)

1

4

3

2

5

Tc

+

-

RTD

7

6

9

8

10

14V

DC

DATA-

DATA+

RS-485

11

14

15

13

12

AC 100~240V

50/60 Hz

5VA

3A

250Vac

ALM 2

ALM 1

COM

3A

250Vac

NO

OUT1

14V

or

4~20mA

or

0~10V

DC

+

-

COM

NO

COM

+

-

IN

OUT2/
ALM3

+

-

L

N

DTB4896

DTB9696

DTB4896/DTB9696

NO

COM

NC

5A

250Vac

1

4

3

2

5

7

6

9

8

10

11

14

15

13

12

16

19

20

18

17

AC 100~240V

50/60 Hz

5VA

OUTPUT1

14VDC

4~20mA

0~10V

NO

COM

NC

5A

250Vac

OUTPUT2/ALM3

14VDC

ALM2

COM

or

or

Tc

+

RTD

DATA+

DATA-

RS-485

SG

Ev1

Ev2

CT

ALM1

COM

IN

+

+

-

+

- -

-

L

N

DTB9696RRV

 

External Dimensions

Dimensions are in millimeter (inch)

„

DTB4824

„

DTB4848

48.0 mm

(1.89 in)

2

4

.0

m

m

(0

.9

4

in

)

3.4 mm

(0.13 in)

99.8 mm
(3.93 in)

2

1

.8

5

m

m

(0

.8

6

in

)

44.75 mm
(1.76 in)

2

2

.0

m

m

(0

.8

7

in

)

44.8 mm

(1.76 in)

48.0 mm
(1.89 in)

4

8

.0

m

m

(1

.8

9

in

)

9.5 mm
(0.37 in)

80.0 mm
(3.15 in)

4

4

.7

5

m

m

(1

.7

6

i

n

)

45.0 mm
(1.77 in)

+0.6

0

4

5

.0

m

m

(1

.7

7

i

n

)

+

0

.6

0

+0.02

0

+

0

.0

2

0

„

DTB4896

„

DTB9696

48.0 mm
(1.89 in)

12.8 mm
(0.50 in)

79.2 mm(3.12 in)

91.0

m

m

(3.58

in

)

95.

7

m

m

(3

.77

in

)

98.2

m

m

(3

.8

7 in

)

44.0 mm
(1.73 in)

44.5 mm
(1.75 in)

+0.6

0

91.5

m

m

(3

.6

0 in

)

+0

.6

0

+0.02

+0

.0

2

0

0

96.0 mm
(3.78 in)

96

.0

mm

(3

.7

8

in

)

98

.0

mm

(3.

8

6 in

)

15.8 mm
(0.62 in)

79.2 mm
(3.12 in)

90

.8

m

m

(3

.5

7

in

)

91.0 mm
(3.58 in)

+0.6

0

91

.0

mm

(3.

5

8 in)

+0

.6

0

+0.02

0

+0

.0

2

0

 

Mounting

„

Mounting Method

„

Mounting Bracket Installation

„

CT Wiring Method (if CT function is selected)

Step 1 : Insert the controller through the panel cutout.

Step 2 : Insert the mounting bracket into the mounting

groove at the top and bottom of the controller

Step 3 : Push the mounting bracket forward until the

bracket stops at panel wall.

Step 4 : Insert and tighten screws on bracket to secure the

controller in place. (The screw torque should be

0.8kgf-cm to 1.5kgf-cm)

DTB4824 Mounting Method:

DTB4848/4896/9696 Mounting Method:

1

3

2

06

.8

m

m

M

ax

.

 

Error Acknowledgement & Display

Communication error code response description:

Error Status 102EH / 4750H

PV read back 1000H / 4700H

Error status

0001H M/A

PV

unstable

0002H

8002H

Re-initial, no temperature at this time

0003H

8003H

Input sensor did not connect

0004H

8004H

Input signal error

0005H

N/A

Over input range

0006H 8006H

ADC

fail

0007H

N/A

EEPROM read/write error

Display message:

Power ON

Normal display

PV

DTB series, Firmware V1.50

Present value

SV

Output VR type with Event option

Set value

Sensor didn’t connect

Input error

PV

No

Error

SV

Connect

Input

EEPROM error

Input over range

PV

Error

PV flash when over

SV

EEPROM

 

How to Set Up Current Input

For normal input

For current input (4 ~ 20mA, 0 ~ 20mA)

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at

http://www.delta.com.tw/industrialautomation