Table 1 — System Matches

*Units must be field reconfigured for 1

1

/

2

ton (18,000 Btuh) operation. See Before Installation sec-

tion on page 3 for details.

NOTE: Numbers in ( ) indicate quantities when there is more than one fan coil unit in the system.

Ensure unit operation within the application guidelines

shown in Table 2. When installing the outdoor unit, for cooling

operation when the outdoor-air temperature is below 55 F, the

following accessories are required:
• low ambient kit

• crankcase heater

• winter start kit

• isolation relay (38QRR heat pump units only)

This will provide cooling operation down to 40 F ambient

temperature. For operation down to –20 F ambient tempera-

ture, a field-installed wind baffle will also be required.

To complete installation of the system, the following items

must be field-supplied for connection of the indoor and outdoor

units:
• refrigerant piping

• condensate drain piping

• thermostat

• power and control wiring

For some applications, a fresh air intake, power vent fan,

and/or condensate pump kit may be required.

Table 2 — Application Range

LEGEND

*This value is for single-zone systems and may be equipped with an

accessory low-ambient control or winter start kit that will allow
operation down to

–20 F.

SYSTEM TYPE

INDOOR SECTION NUMBER

OUTDOOR SECTION NUMBER

Cooling Only

40QAC

38HDR-3,5,6

024*

018

024

024

036

030

036

036

048

048

060

060

Heat Pumps

40QAQ

38QRR-3,5,6

024*

018

024

024

036

030

036

036

048

048

060

060

Heating/Cooling

40QAQ

38HDR-3,5,6

024*

018

024

024

036

030

036

036

048

048

060

060

COOLING

Maximum

Minimum

Indoor

Outdoor

Indoor

Outdoor

95 F DB

71 F WB

125 F DB

67 F DB

57 F WB

55 F DB*

40 F DB

HEATING (Heat Pump Systems Only)

Maximum

Minimum

Indoor

Outdoor

Indoor

Outdoor

80 F DB

71 F WB

75 F DB

65 F WB

55 F DB

–20 F DB

DB

Dry Bulb

WB

Wet Bulb