beautypg.com

Step 6 — make electrical connections – Carrier 40QA024-060 User Manual

Page 10

background image

10

Step 6 — Make Electrical Connections —

Be sure

field wiring complies with local building codes and NEC, and

unit voltage is within limits shown in Table 5.

Contact local power company for correction of improper

line voltage.

NOTE: Use copper wire only between disconnect switch(es)

and unit.
NOTE: Install branch circuit disconnect of adequate size to

handle unit starting current per NEC. Locate disconnect within

sight of, and readily accessible from, unit, per Section 440-14

of NEC. Some codes allow indoor unit to share disconnect with

outdoor unit if disconnect can be locked; check local code

before installing in this manner.

1. Route ground and power wires.

2. Route line power leads (see Fig. 16) from indoor dis-

connect to the fan coil unit. Place wire through hole on

the control box (Fig. 17). Connect wire to high voltage

terminal board (TB1) and ground screw. When routing

the wire in the unit, use care to keep the wire away

from refrigerant and condensate piping and any sharp

edges. The 208/230-v units are factory wired for

230-v to 24-v transformer operation. For 208-v to

24-v operation, interchange blue (208-v) and red

(230-v) wires. Cap any unused wires with wire nuts.

Table 5 — Electrical Data*

LEGEND

*All units are 208/230-1-60. Minimum operating voltage is 187, max-

imum is 253. Units will operate satisfactorily within this voltage
range.

†Electrical data is the same for both the 24,000 Btuh 024 unit and

the 024 unit that has been field-reconfigured for 18,000 Btuh. Refer
to Before Installation section on page 3 for reconfiguration details.

To avoid personal injury or damage to unit, do not make

electrical connections until all power sources are shut

down, locked out, and tagged off. Failure to do so could

result in personal injury or unit damage.

Operation of unit on improper line voltage constitutes abuse

and could affect warranty. Refer to Table 5 for permissible

operating limits. Do not install unit in system where voltage

may fluctuate above or below permissible limits.

According to NEC and most local codes, the unit must have

an uninterrupted, unbroken ground to minimize personal

injury if an electric fault should occur. The ground may

consist of electrical wire or metal conduit when installed in

accordance with existing electrical codes. Failure to follow

this warning could result in an electric shock, fire, or death.

SYSTEM

TYPE

UNIT

SIZE

FAN

HEATER

POWER

MIN WIRE SIZE

(AWG)

Motor 1 FLA

Motor 2 FLA

kW

FLA

MCA

MOCP

FLA

COOLING
ONLY

024†

0.5

0.53

15

0.50

14

036

1.3

1.60

15

1.30

14

048

1.1

0.5

2.00

15

1.60

14

060

1.3

1.3

3.30

15

2.60

14

HEAT PUMP

024†

0.5

2.00

8.66

9.29

15

9.16

14

036

1.3

3.00

13.00

17.70

20

14.30

14

048

1.0

0.5

4.00

17.40

23.80

25

19.00

12

060

1.3

1.3

5.00

21.70

28.70

30

24.30

10

AWG

American Wire Gage

FLA

Full Load Amps

MCA

Minimum Circuit Amps per NEC Section 430-24

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code