Step 14—Check Charge

UNIT CHARGE

Factory charge is shown on unit rating plate. To check charge in
cooling mode, refer to Cooling Only Procedure. To check charge
in heating mode, refer to Heating Check Chart Procedure.

COOLING ONLY PROCEDURE

NOTE:

If superheat or subcooling charging conditions are not

favorable, charge must be weighed in accordance with unit rating
plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft
respectively.

EXAMPLE:

To calculate additional charge required for a 25-ft line set:

25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge

Units installed with cooling mode TXV require charging with the
subcooling method.

1. Operate unit a minimum of 10 minutes before checking

charge.

2. Measure liquid service valve pressure by attaching an accurate

gage to service port.

3. Measure liquid line temperature by attaching an accurate

thermistor type or electronic thermometer to liquid near
outdoor coil.

4. Refer to Heat Pump Charging Instructions label on outdoor

unit.

5. Refer to Table 4. Find the point where required subcooling

temperature intersects measured liquid service valve pressure.

6. To obtain required subcooling temperature at a specific liquid

line pressure, add refrigerant if liquid line temperature is
higher than indicated or reclaim refrigerant if temperature is
lower. Allow a tolerance of ± 3°F.

HEATING CHECK CHART PROCEDURE

To check system operation during heating cycle, refer to the HEAT
Pump Charging Instructions label on outdoor unit. This chart
indicates whether a correct relationship exists between system
operating pressure and air temperature entering indoor and outdoor
units. If pressure and temperature do not match on chart, system
refrigerant charge my not be correct. Do not use chart to adjust
refrigerant charge.

NOTE:

In heating mode, check refrigerant charge only when

pressures are stable. If operating conditions cause PressureGuard
switch to open and outdoor fan to cycle, check refrigerant charge
in cooling or lower indoor dry bulb temperature. If in doubt,
remove charge and weigh in correct refrigerant charge.

NOTE:

When charging is necessary during heating season,

charge must be weighed in accordance with unit rating plate ± 0.6
oz/ft of 3/8-in. liquid line above or below 15 ft respectively.

EXAMPLE:

To calculate additional charge required for a 25-ft line set:

25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge

Fig. 19—Defrost Control

A99442

OF2

CESO130076–00

OF1

ON

Q

UIET

SHIFT

120

30

60

60

30

90

INTER

V

AL

TIMER

OFF

P3

DFT

O R

W

2

Y C

T2 C C O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

14