COMBINATION RATINGS
i 38GR006 and 40BA009
Ratings Notes
1. Direct interpolation is permissible. Do not
extrapolate.
2. SHC is based on 80 F db temperature of air
entering evaporator coil.
Below 80 F db, subtract (corr factor x cfm)
from SFIC.
Above
80 F
db, add (corr. factor
x
drn) to
SHC.
ENTERING AIR DRY -BULB TEMP (F)
BYPASS
79
78
77
76^
— r
75 1 under 75
FACTOR
81
85
ovec/85
Correction Factor
.10
97
1.95
2 92
3 89
4.86
use formula
.20
86
1 73
2.59
3 46
4 32
.30
76
...
1 51
2.27
3 03
3 78
shown be low
Interpolation is permissible
Correction Factor = 1 08 x (1
BF) X (db - 80)
3. Gross capacities shown do not include a deduc
tion for evaporator fan motor heat.
4. Formulas:
hdb “ tedb
sensible heat capacity (Btuh)
1.08 X cfm
tiwb “ wet-bulb temperature corresponding to
enthalpy of air leaving evaporator coil
(hlwb)
hlwb - hewb
total capacity (Btuh)
4.5 X cfm
where hewb ~ enthalpy of air entering evap coil
5. Combination ratings are based on a 2 F line
loss. For a close-coupled system (less than
15 ft),
add 2%
to ratings. Piping sizes in Table
13 are based on 2 F line loss. All combination
ratings are based on R-22.
T emp(F)
Air Ent
2875/. 13
Evgp Air - Cfm/BF
3825/. 16
4775/. 19
Evap Air - Ewb (F)
72
67
62
72
67
62
72
67
62
TC
81
74
69
83
77
74
84
78
77
85 SHC
46
60
69
53
70
74
59
76
77
KW
8.2
7.7
7.4
8.3
7.9
7.7
8.4
8.0
7.9
TC
75
69
65
77
71
69
78
72
72
95 SHC
44
57
65
51
67
69
57
72
72
KW
8.7
8.2
7.9
8.9
8.4
8.3
9.0
8 5
8.5
TC
72
66
63
74
68
67
74
69
70
100 SHC
43
58
63
50
65
67
56
69
70
KW
8.9
8.4
8.2
9.1
8.6
8.5
9.2
8.8
8.8
TC
69
64
61
71
66
65
71
67
67
105 SHC
42
56
61
49
64
65
55
67
67
KW
9.2
8.7
8.4
9.4
8.9
8.8
9.5
9.0
9.0
TC
63
59
57
64
60
60
65
62
62
115 SHC
40
53
57
47
60
60
53
62
62
KW
9 6
9.1
8.9
9.8
9.3
9.3
9.9
9.5
9.6
38BA008 and 40BA009
ARI - 88,000 Btuh
Temp(F)
Air Ent
Evap Air - Cfm/BF
2500/. 16
3400/.23
4300/.28
Evap Air - Ewb (F)
72
67
62
72
67
62
72
67
62
TC
101
93
85
105
97
89
108
99
91
85 SHC
50
62
74
55
70
86
59
70
91
KW
7.7
7.4
7.0
7.8
7.6
7.2
7.9
7.6
7.3
TC
96
89
81
100
92
85
102
94
87
95 SHC
48
60
72
53
68
84
57
75
87
KW
8.4
8.0
7.6
8.5
8.2
7.8
8.6
8,2
7.9
TC
94
86
79
98
89
83
100
91
85
100 SHC
48
59
71
52
68
81
56
74
84
KW
8.7
8.4
7.9
8.9
8.5
8,1
8.9
8.6
8,2
TC
91
84
77
95
87
80
97
89
82
105 SHC
47
58
70
52
67
80
55
73
82
KW
9.1
8.7
8.2
9,3
8.9
8.4
9.4
9.0
8.5
TC
86
79
73
90
82
75
91
84
77
115 SHC
45
57
68
50
65
75
53
71
77
KW
9.8
9.4
9.0
9.9
9.5
9.1
10 1
9.7
9.3
^^38BA009 and 40BA009
AR
- 100,000 Btuh
Evap A ir - Cfm/BF
Air Ent
2500/. 16
3400/.23
4300/.28
Ci
E vap Air - E wb (F)
72
67
62
72
67
62
72
67
62
TC
112
103
94
118
108
99
121
112
102
85 SHC
54
67
79
59
75
90
64
82
101
KW
10.5
9.9
9.5
10.7
10.2
9.7
11,1
10.5
9.9
TC
108
99
90
113
104
95
1 16
107
98
95 SHC
53
65
77
58
73
88
62
80
98
KW
11.2
10.7
10.2
11.6
11,0
10,5
11.9
11,3
10.6
TC
105
96
89
no
101
93
113
104
95
100 SHC
52
64
76
57
72
87
61
79
95
KW
1 1.6
11.1
10.5
12.0
1 1.4
10,8
12.3
11.7
10,9
TC
102
94
86
106
98
90
109
101
92
105 SHC
51
63
75
56
71
86
60
78
92
KW
12.0
11.4
10.8
12.5
11.8
11.0
12.7
12.1
1 1.3
TC
96
89
81
101
92
83
103
95
87
115 SHC
49
61
72
54
69
83
58
76
87
KW
12 8
12 2
1 1 6
13 2
12 5
11 9
13 4
12 7
12 1
38GR006 and 40RR008
LEGEND
E vap Air — Cfm/BF
2525/. 19
3375/.23
42257.26
BF — Bypass Factor
r.
E vap A ir — Ewb (F)
TC — Total Capacity (1000 Btuh)
72
67
62
72
67
62
72
67
62
SHC — Sensible Fleating Capacity (1000 Btuh)
TC
79
71
65
81
74
70
83
76
74
KW >- Compressor Motor Power Input
85 SHC
43
55
65
50
64
70
56
72
74
Ewb — Entering Wet-Bulb
KW
7.7
7,2
6.9
7.9
7,4
7.2
8.0
7.6
7.4
U - Upper Coil
TC
73
67
62
75
69
66
76
71
69
M — Middle Coil
95 SHC
41
54
62
48
62
66
53
69
69
L — Lower Coil
KW
8.2
7.7
7.4
8.1
7.9
7.7
8.5
8.1
7.9
U-M-L abbreviations indicate connection of condensing unit to upper.
TC
71
64
60
73
67
64
74
68
67
middle or lower coil of fan-coil unit
100 SHC
40
53
60
47
61
64
52
67
67
KW
8.4
8.0
7.6
8.6
8.2
7,9
8.7
8.3
8.2
TC
68
62
58
70
64
62
71
66
65
105 SHC
39
52
58
46
60
62
51
65
65
KW
8.7
8.2
7.9
8.9
8.4
8.2
9,0
8.5
8,4
TC
63
58
55
65
60
58
65
61
61
115 SHC
38
50
55
44
57
58
49
61
61
KW
9.1
8.6
8.3
9.3
8.8
8.7
9 4
8.9
8 9