Table 3 - Motor Overload Module

Calibrating Electronic Controls

- Honeywell (Fig. 4) or Barber-Colman (Fig. 5)

SEQUENCE

H

B-C

PROCEDURE

1. Check Voltage Signal

from current trans­
former - (leads
disconnected)

X

X

A. Shut down compressor:

X

1. Rotate CRl (6) and CR2 (7) calibration screws fully clockwise.

X

X

2. Disconnect leads to terminals 23 and 24 on terminal strip.

Attach voltmeter to these leads.

X

X

3. Place clamp on ammeter on one of three incoming starter wires.

X

X

B. Start compressor:

X

X

1. Press START button.

X

2. Open vanes manually by depressing INCREASE button (5).

X

3. Place the capacity control switch (15) on HIGHER position to

open vanes manually.

NOTE; At- iOO percent Ml load current^ voltmeter must

read at least 0.55 volts. If not in this range, check sizing

of resistor in starter.

2. Recheck voltage

signal (leads

connected)

X

X

A. Shut down compressor:

X

X

1. Remove voltmeter from leads.

X

X

2. Replace leads to terminals 23 and 24.

X

X

3. Attach voltmeter to terminals 23 and 24.

X

X

B. Start the compressor:

X

X

1. Open vanes manually. Voltmeter must read between 0.45-0.55

volts at 100 percent full load current.

X

X

2. Press STOP button and remove voltmeter.

3. Calibrate motor

current settings
(compressor
operating)

X

A. Barber-Colman:

1. Open vanes manually until motor current reaches 108 percent

of nameplate current.

X

2. Adjust CRl calibration screw (6) until vanes begin to close.

Observe movement of vane motor linkage.

X

3. Set capacity control switch (15) on HIGH. When motor reaches

103 percent of full load amperage, adjust CR2 calibration

screw (7) until vanes stop moving.

X

B. Honeywell:

1. When motor current reaches 103 percent of rated amperage,

adjust calibration screw (18) until relay CR2 (23) is open and
relay CRl (22) is closed.

X

2. Hold relay CR2 (23) closed, and open vanes with INCREASE

button (5). When motor current reaches 108 percent of rated

amperage, relay CRl (22) should open.

X

X

C. Honeywell and Barber-Colman:

1. Close vanes and open again to recheck 103 percent and 108

percent settings.

m

H = Honeywell
B-C = Barber-Colman