beautypg.com

A warning, Heat anticipator settings for room thermo – Carrier 38QH User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HEATING A COOLING

38QH

Heat Pumps — Outdoor Section

Table 3 — Electrical Data (60 Hz)

3-Phase Available with 030-060 Sizes (SM, DL Option Models)

OUTDOOR

UNIT 38QH

V/PH

OPER VOLTS*

COMPR

FAN

FLA

BRANCH CIRCUIT

MCA

Max Fusef

or HACR Type

Ckt Bkr Amps

Max

Min

LRA

RLA

015301

35

7 1

7

8 6

15

018301

50

8 0

7

12 3

20

024301

54

12 9

9

15 3

25

030301

78

14 5

9

20 3

35

036301

208/230/1

254

187

86 7

14 9

9

21 3

35

042301

107 4

18.3

1 9

27 3

45

048301

110

20 4

1 9

29 9

50

060331

130

25 9

1 9

34 3

60

060341

142

31 2

1 9

40 9

60

030501

59.5

10 6

.9

15 4

25

036501

65

11.5

.9

16 5

25

042501

208-230/ЗФ

245

187

74

133

9

19 1

30

048501

92

147

1 9

20 9

35

060531

Not Available

036601
042601
048601
060631

460/Зф

506

414

32 8

37
46

5 1

62
70

1 1

1.3
1 3

Not Ava

7.5

9 1

10.1

liable

15
15

15

FLA

— Full Load Amps

HACR

— Heating, Air Conditioning, Refrigeration

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

RLA

— Rated Load Amps

'Permissible limits of the voltage rangeât which unitwill operate satisfactorily

fTime-delay fuse.
|3-Phase available only with Deluxe and SM option units.

NOTE: Control circuit is 24 v on all units and requires external power source.

A

WARNING

To avoid personal injury, be sure indoor blower has

stopped before attempting service or maintenance.

pump shutdown. When one outdoor thermostat is used,

a supplemental heat relay is not required. The supple­

mental heat switch in the indoor thermostat subbase
bypasses outdoor thermostat, locks out compressor and
activates electric heater.

Heat Anticipator Settings for Room Thermo-

Stat(HH01AT171) — Set anticipator for room thermo­

stat according to Table 4. These settings may be changed

slightly to provide a greater degree of comfort for a par­

ticular installation.

MOUNT OUTDOOR THERMOSTAT in control box.

Attach brackets with short sheet metal screws to avoid

contact with coil. Leave capillary tube coiled in control
compartment making sure it is clear of all electrical con­

nections and sharp metal edges.

Accessory Outdoor Thermostat provides adjust­

able outdoor control of accessory electric heater. This

thermostat makes contact when a drop in outdoor tem­

perature occurs. It energizes a stage of electric heat
when the outdoor temperature setting is reached, pro­

vided the room thermostat is on the second stage of heat­

ing. One outdoor thermostat is recommended for each
stage of electric heat after the first stage. Set the outdoor
thermostat(s) progressively lower for each stage. Refer
to heat load of building and unit capacity to determine
the correct outdoor thermostat settings.

The accessory supplemental heat relay is required when

2 outdoor thermostats are used. It is automatically ener­

gized by the manually operated supplemental heat switch
in the indoor thermostat subbase. The thermostat locks
out compressor and the relay bypasses the outdoor
thermostats for electric heater operation during heat

MOUNT SUPPLEMENTAL HEAT RELAY in con­

venient location on indoor unit. Attach with sheet metal
screw.

Table 4 — Thermostat Anticipator Settings

UNIT

38QH

FIRST-

STAGE

ANTICIPATOR

SETTING

INDOOR

UNIT WITH

ELECTRIC

HEATER

HTR

kW

SECOND-

STAGE

ANTICIPATOR

SETTINGS

015
018
024
030
036

042

048

060

Fixed

40DQ and

40AQ Fan Coil

with 40AQ FItrs

or 40QB Fan Coil

with 40QB Htrs

50

7 5

10.0

25

15 0

20 0
25.0

50

30 0
34.0

75

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Booklll4

PC101

Catalog No 533-808

PrintedinUSA

Form38QH-2SI

Pg 5

7-85

Replaces: 38QH-1 SI

For replacement Items use Carrier Specified Parts

Tab I5al5a