Start-up, adjustment, and safety check, Gas input, A caution – Carrier 58SX040 User Manual
Page 6
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
START-UP, ADJUSTMENT, AND
SAFETY CHECK
Adjusting Tuning Valve — Before firing the furnace,
adjust the pressure drop through the heat exchanger for
maximum efficiency, following the steps below
A CAUTION
Be sure gas supply to furnace is turned off.
1, Install field-supplied plastic tee between pressure tap
on bottom of gas valve and pressure tube as shown
in Fig. 6.
2
Install second field-supplied plastic tee between
pressure switch and pressure tube from collectoi box
See Fig 6.
3 Connect slope gage to tees (Fig. 6)
4. Close R-W circuit to start inducer motor.
5. Adjust tuning valve to obtain 0.83 ± 0 01 in negative
water column.
6 Remove handle from tuning valve and recheck pres
sure. Store handle in safe place.
7. Open R-W circuit.
8 Disconnect slope gage
9. Remove plastic tees and reconnect factory pressure
tubes to gas valve and pressure switch.
10 Turn on gas supply to furnace
Ignition System Check — When all connections
have been checked, light the furnace using procedure
outlined on lighting instruction plate attached to furnace
When lighting the furnace for the first time, however,
perform the following additional steps
1 If gas supply was not purged before connecting
furnace, line will be full of air Loosen ground joint
union and allow supply line to purge until gas odor is
detected. Neva purge gas lines into a comhustion
chamber. Immediately upon detection of gas odor,
retighten union. After 5 minutes, light furnace in
accordance with instructions on furnace rating plate.
2 Main burners should light 25 to 75 seconds after pilot.
If main burners do not light within prescribed time
period, adjust pilot flame, allow pilot to cool for
5 minutes, and repeat time check (Fig. 7).
3 Locate pilot adjusting screw on top of valve;
a. Remove cap screw, turn pilot adjusting screw
counterclockwise to decrease burner-on time delay,
or clockwise to increase burner-on time delay.
b. Replace cap screw.
Gas Input
NOTE: Be sure reference pressure tube, combustion-air
and vent pipes, and burner enclosure front are in place
when clocking the gas meter.
1. Deteimine gas input.
a. Turn off all other gas appliances and pilots
b. Measure time (in seconds) for gas meter test dial to
complete one revolution
c Refer to Table 4 for cu ft of gas per hour,
d. Multiply cu ft/ hr by heating value of gas (Btu/ cu ft)
obtained from local gas utility.
EXAMPLE
Btu heating input = Btu/cu ft times cu ft/hr
Heating value of gas = 1070 Btu/cu ft
Time for one revolution of 2-cu-ft dial = 72 sec
Gas rate = 100 cu ft/hr (frbm Table 4)
Btu heating input = 107() x 100 = 107,000 Btuh
e. Measured gas input must not exceed gas input on
unit rating plate.
2. To adjust input rate:
a.
Remove burner enclosure front and cap that
conceals adjustment screw for gas valve regulator.
b. Turn adjusting screw either counteiclockwise (out)
to decrease input rate or clockwise to increase rate.
When adjusting input rate, do NOT change mani
fold pressure more thanO.3 in wg. Make any major
adjustments by changing main burner orifices
(Fig. 7).
Table 4 — Gas Rate in cu ft/hr
SECONDS
FOR ONE
REVOLU
TION
SIZE OF
TEST DIAL
SECONDS
FOR ONE
SIZE OF
TEST DIAL
1
cu ft
2
cu ft
5
cu ft
REVOLU
TION
1
cu ft
2
cu ft
5
cu ft
10
360
720
1800
50
72
144
360
11
327
655
1636
51
71
141
355
12
300
600
1500
52
69
138
346
13
277
555
1385
53
68
136
340
14
257
514
1286
54
67
133
333
15
240
480
1200
55
65
131
327
16
225
450
1125
56
64
129
321
17
212
424
1059
57
63
126
316
18
200
400
1000
58
62
124
310
19
189
379
947
59
61
122
305
20
180
360
900
60
60
120
300
21
171
343
857
62
58
116
290
22
164
327
818
64
56
112
281
23
157
313
783
66
54
109
273
24
150
300
750
68
53
106
265
25
144
288
720
70
51
103
257
26
138
277
692
72
50
100
250
27
133
267
667
74
48
97
243
28
129
257
643
76
47
95
237
29
124
248
621
78
46
92
231
30
120
240
600
80
45
90
225
31
116
232
581
82
44
88
220
32
113
225
563
84
43
86
214
33
109
218
545
86
42
84
209
34
106
212
529
88
41
82
205
35
103
206
514
90
40
80
200
36
100
200
500
92
39
78
196
37
97
195
486
94
38
76
192
38
95
189
474
96
38
75
188
39
92
185
462
98
37
74
184
40
90
180
450
100
36
72
180
41
88
176
439
102
35
71
178
42
86
172
429
104
35
69
173
43
84
167
419
106
34
68
170
44
82
164
409
108
33
67
167
45
80
160
400
110
33
65
164
46
78
157
391
112
32
64
161
47
76
153
383
116
31
62
155
48
75
150
375
120
30
60
150
49
73
147
367