beautypg.com

Carrier 07E User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Check low-pressure switch by slowly closing

suction shutoff valve or by completely closing
hquid line shutoff valve. A decrease of suction
pressure will follow. Compressor should shut off
within 4 psi of values shown in Table 1.

HIGH-PRESSURE
SAFETY SWITCH

LOW-PRESSURE
SAFETY SWITCH

RANGE ADJUSTMENT-TURN

CLOCKWISE TO RAISE BOTH
CUT-IN AND CUTOUT

DIFFERENTIAL ADJUSTMENT -TURN

■ № ■' CLOCKWISE TO DECREASE ONLY LOWER

SETTING WITHOUT CHANGING THE
HIGHER SETTING

*Hlgh — 38 PsI/Turn

Low — 7 Psi/Turn

Fig. 8 — Dual Pressurestat Adjustment

Time Guard Circuit

for each compressor provides

for a 5-minute delay before restarting compressor
after shutdown for any reason. On starting, the
Time Guard Timer causes a delay of 15 seconds

after thermostat closes before compressor will
start. On compressor shutdown, the timer recycles
for 4 minutes 45 seconds. During this time the

compressor cannot restart.

Compressor Motor Protection

on 06EW027,

06EW044, 07EB027 and 07ED044 consists of
three temperature sensors embedded in motor
windings and connected to a solid state module in
unit control box.

When an over-temperature condition causes

module to shut compressor off, push control
center STOP button. Investigate cause of com­
pressor shutdown and correct. After compressor
cools (see Temperature Sensors below), push
ST ART-RESET button. Compressor will restart
after Time Guard delay period.
SOLID STATE MODULE is checked by applying
unit control voltage to terminals T1 and T2 (see
label diagram), then checking for continuity across
terminals Ml and M2. If no continuity between Ml
and M2, check temperature sensor and fuse resist­
ance using a volt-ohmmeter (see below).

CAUTION; Do not use a fcattiary powered test

lamp

to check sensors. Excessive current can

cause damage.

TEMPERATURE SENSORS are protected by
three 1/8-amp fuses (Carrier Part no. HYIOLFOIO)
in compressor terminal box. Fuse resistance should
be between 3.2 and 4.4 ohms. Replace defective
fuses only with 1/8-amp fuses specified above. If

all sensors check below 95 ohms (180 F), fuses are
good, and there is no continuity between module
terminals Ml and M2, replace module.

If one sensor fails, it can be jumpered out of

the circuit with a 75 ohm, 2-watt resistor across
the proper sensor terminal and common terminal.
If a short to ground in sensor circuit is indicated,

replace compressor motor.

CAPACITY CONTROL ADJUSTMENT

Control Set Point

(cylinder load point) is adjust­

able from 0 psig to 85 psig. Pressure differential
between cylinder load-up point and cylinder un­
load point is adjustable from 6 psig to 22 psig.

To Regulate Control Set Point

— Refer to Fig. 9.

Turn adjustment nut clockwise to its bottom stop
(with nut in this position set point is 85 psig).
Control set point is then regulated to desired
pressure by turning adjustment nut counterclock­
wise; every full turn decreasing set point by 7.5 psig.
(Approximately 11-1/2 turns in counterclockwise
direction will decrease control set point to 0 psig.)

Table 3 shows the steps of control for the

compressor and condensing unit.

SEALING CAP
(CAP MUST BE REPLACED
TO PREVENT REFRIGERANT LEAKAGE)

Fig. 9 — Capacity Control Valve

Table 3 — Steps of Control

COMPRESSOR*

1

STEPS

2

--------------- -

3

CONDENSING

UNIT*

No.

Cyl

%

Cap.

No.

Cyl

%

Cap.

No.
Cyl

%

Cap.

06EV022
07EB022

4

100

2

50

-

-

06EW027

07EB027

6

100

4

67

2

33

06EW033

07EB033

6

100

4

67

2

33

06EW044

07ED044

6

100

4

67

2

33

^Capacity control valve (Fig 6) factory settings for 4-cylinder

units are: 69 psig control set point (cylinder load point), 10 psig

differential

(59

psig

cylinder

unload

point)

Settings

for

6-cylinder units are; leit cylinder bank control set point is
70 psig, differential is 10 psig; right cylinder bank control set
point is 68 psig, differential is 10 psig