beautypg.com

Step 4 — set indoor fan motor speed — all, Start-up, 50et,qt single-package units – Carrier 50ET User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HEATING A COOLING

50ET,QT

Single-Package Units

(5>

S>]

(5>

JM.

JH

JZL

_0_

WIRES FROM

UNIT CONTROL BOX

THERMOSTAT AND
SUBBASE (SEE BELOW)

UNIT CONTROL BOX

WIRING TERMINAL BOARD

THERMOSTAT

SUBBASE

99TZ900321

99TZ900361

99TZ900321

99TZ900391

THERMOSTAT/SUBBASE

99TZ900291
99TZ900401
99TZ900511
99TZ900541

COOLING UNIT WITH ELECTRIC HEAT

HEAT PUMP WITH SUPPLEMENTAL ELECTRIC HEAT

Fig. 4 — Thermostat Connection Diagrams — 50ET,QT

3. Route thermostat wires through hole located on left

coil partition and up to low-voltage wire entrance
hole on control box front cover.

4. Remove 2 screws and slide control box to expose

low-voltage terminals. Attach wires to appropriate
terminals as shown on unit wiring diagram. See Fig. 4.

5. Attach thermostat to subbase and snap on thermostat

cover.

6. Cut and remove insulation from hole in metal cover

plate.

7. Replace metal cover plate.
8. Install accessory polymer front cover as described in

instructions

shipped

with

accessory

cover.

Cut

rectangular hole for thermostat as indicated by mark
in back of cover.

TO MOUNT THERMOSTAT REMOTELY-

1.

Pull

field-supplied

thermostat

wires

previously

installed up into wire entrance hole on control box
front cover and connect wires as described in Step 3,
paragraph 4, above.

2. Connect other ends of thermostat wires, hanging from

the wall at their remote location, securely into subbase
at appropriate terminals specified in unit wiring
diagram. See Fig. 4.

3 Mount subbase onto wall.
4.

Attach thermostat to subbase. Snap on cover and

install chassis indoor cover.

Step 4 — Set Indoor Fan Motor Speed — All
units are factory wired for low fan speed. Higherexternal
static pressure requirements can be met by wiring motor
for higher fan speed. See Table 3.

Step 5 — Install Accessory Electric Heater,

If Required — Refer to instructions packaged with

accessory heater. See Table 2 for part numbers.

»

Table 3 — Service Data

SIZE

212

215

218

224

230

MODEL 50

ET I QT

ET lOT

ET 1 QT

ET 1 QT

ET 1 QT

R-22 CHARGE* (lb)

Refrig Control

2 3 I 2 7

2 3 ) 2 7

AccuRa

3 1 1 3 75

ter'" BypaE

4.0 1 4 5

s Type

3 9 ) 4 7

INDOOR FAN

Rotationt
Rpm
Diameter (in.)

Width (In.)

Range (cfm)

Motor Hp

Centrifugal Blower,

Direct Drive, 2-Speed

CW I CW I CW I CCW I CCW

1580 1550 1570 1675 1675

6 1 6 1 6 1 7 1 7

8

430/ 1 550/ 1 575/ 1 885/ 1 1025/

375 475 480 800 960

V. 1 '/, 1 % 1 '/4 1 '/4

OUTDOOR FAN

Ctm
Rpm
Diameter (In
)
Motor Hp

Propeller, Direct Drive, Single Speed

1700 1 1700 1 2000 1 2000 1 2000

1125

15
’/

b

CCW

Counterclockwise

CW — Clockwise

‘Factory

refrigerant

charge

tLooking at fan motor shaft

START-UP

Crankcase Heater — The 50QT compressor is
equipped with a crankcase heater that is thermostatically

activated in cold weather. (See Fig. 2 and 3.) If tempera­
ture is below 65 F, operate crankcase heater 24 hours

before starting unit. To energize crankcase heater only,
after

chassis

installation,

set

thermostat

to

^^

position (for thermostat mounted on the chassis) or OFF
position (for remote-mounted thermostat) and turn on
unit power at disconnect switch.

t

Bookn

1 1

|4 |4

PC 131 Catalog No 535-078 PrintedinUSA

Form 50ET.QT-3SI Pg4 5-85 Replaces 50QT-10SI

Tab llbisahalsa

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.

For replacement items use Carrier Specified Parts