Outdoor fan/motor removal, 50et,qt single-package units – Carrier 50ET User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HEATING A COOLING

50ET,QT

Single-Package Units

MODEL 50ET,QT

DIMENSION A

(in.)

212,215

2'h

218,224,230

2

Outdoor Fan/Motor Removal

1. Shut off power to unit.

2. Remove ehassis from sleeve as described previously

in Outdoor Coil Cleaning section.

3. Remove 4 nuts from outer tip of coil support rods and

remove wire mesh guard.

4. Remove fan blade from motor shaft by loosening hub

setscrews and slipping it off shaft.

5. Remove fan motor leads from electrical components

in indoor side control box and pull through bulkhead
so they are loose in outdoor machine compartment.

6. Remove nuts and bolts connecting 4 motor ears to

motor support struts.

7. Remove motor and leads.
8. Reassembly is reverse of above procedure. Make sure

guard is replaced and fan is positioned correctly
as in Fig. 2.

Fig. 19 — Outdoor Fan Position

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.

Book |1 h |4 |4

PC131 Catalog No 535-078 Printed in U S A Form 50ET,QT-3SI Pg12 5-85 Replaces; 50QT-10SI

For replacement items use Carrier Specified Parts

Tab llbl5alla|5a