Outdoor Fan/Motor Removal
1. Shut off power to unit.
2. Remove ehassis from sleeve as described previously
in Outdoor Coil Cleaning section.
3. Remove 4 nuts from outer tip of coil support rods and
remove wire mesh guard.
4. Remove fan blade from motor shaft by loosening hub
setscrews and slipping it off shaft.
5. Remove fan motor leads from electrical components
in indoor side control box and pull through bulkhead
so they are loose in outdoor machine compartment.
6. Remove nuts and bolts connecting 4 motor ears to
motor support struts.
7. Remove motor and leads.
8. Reassembly is reverse of above procedure. Make sure
guard is replaced and fan is positioned correctly
as in Fig. 2.
Fig. 19 — Outdoor Fan Position