Performance data (cont), Application data electrical data (60-hz), Performance data – Carrier WEATHERMASTER 38HQ User Manual
Page 6: Application data electrical data, Cont)
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Performance data
(cont)
INTEGRATED HEATING CAPACITIES* (At Second Stage — both compressors operating)
INDOOR Í OUTDOOR]
COMPR
Í
COIL
I
SECTION; SgCTiON- l
зёно" 1"
INDOOR
UNIT
Fan
Coil
-13
Cap."] Kw
TEMPERATURE OF AIR ENTERING OUTDOOR COIL (Edb F)
17
Cap. ; Kw ■ Cap. ; Kw
27
Cap. : Kw ! Cap. ; Kw
32
37
42
Cap. i Kw I Cap. i Kw ; Cap. I Kw:
227
940
|40FS160
28HQ/VQ036
15 5
3 5
20 0|
3 9
24 5
4 3
29 0
4 5
34 5
5 1 1 37 0
5 3 1
234
960
140FS200
28HQ/VQ042
15 5
4 6
21 5
4 8
27 5
5 0
33 0
5 4
39 5
5 9| 42 5
6 2 I
5 7
6 9
INTEGRATED HEATING CAPACITIES* (At Eirst Stage — one compressor operating)
INDOOR I OUTDOOR]
COMPR i COIL
SECTION i SECTION*
~38Н'а
INDOOR
UNIT
Fan
Coil
TEMPERATURE OF AIR ENTERING OUTDOOR COIL (Edb F)
”27 i.............. ”32
]
37 i 42 М
М7
i 57
Cap. ' Kw : Cap. i Kw ; Cap
Kw ; Cap. : Kw ; Cap. j Kw ; Cap. ; Kw
227 1
940
1 40FS160
28HQ/VQ036 1
21 2
2 7
234 1
. J
960
1 40FS200
28HQ/VQ042 j
24 0
3 6
Cap
Kw
23 6
27 Q
Capacity (1 000 Btuh), includes fan motor heat and deduction
for thermal line losses of 1 5 ft of piping exposed to outdoor
conditions
Power input includes compressor motor power input, indoor
and outdoor fan motor input
Integrated Heating Capacities — Values shown reflect a capacity
reduction at those outdoor air temperatures at which frost forms on
outdoor coil
26 о
2 9
29 5
3 1
33 0 j
3 2
40 5
3 4
50 0 1 3 6
30 5
3 9
34 0
40
38 5
1
4 1
47 5
4 4
58 Ô 1 4 7
2 8
3 7
NOTE
Heating ratings shown in table are without accessory electric heater
and are based on 70 F db air entering indoor coil, 85% rh air entering
outdoor coil, and ARhrated cfm See Heating Capacity Correction
Factors table to calculate heating capacity and power input at other
cfm's and indoor coil entering air temperature
HEATING CAPACITY CORRECTION EACTORS
CFM/TON* ; CORRECTION ;
дщ j CORRECTION
ENT INDOOR
COIL
FACTORS
Cap, ; Power
ENT INDOOR
COIL (F)
FACTORS
Cap. i Power
400
98
99
65
1 02
99
450
1 0
1 0
70
1 0
1 0
500
1 02
1 01
75
98
1 01
‘Determine cfm/ton from Combination Rating tables
Application data Electrical data
(
60
-Hz)
INSULATION TO VAPOR LINE EXPOSED
TO OUTDOOR CONDITIONS
LENGTH OF EXPOSED
1
INSULATION
VAPOR LINE*
1
THICKNESSt
m
1 (m.)
To
1 3/8
25
1 1/2
35
! 3/4
50
1 3/4
‘Recommended vapor line insulation for piping exposed
to outdoor conditions to prevent loss of heating during
heating cycle When vapor line goes thru interior
spaces, insulation should be selected to prevent con
densation on cooling cycle Heating capacity should be
reduced 1000 Btuh if over 35 ft of vapor line with
3/4-in insulation is exposed to outdoor conditions
(Closed cell foam plastic insulation with a thermal con
ductivity of 28 Btuh/sq ft/F/inch
NOTE Vapor lines of accessory precharged tubing pack
ages (available for use with 38HQ units) are insulated
with closed cell foam plastic insulation with a thermal
conductivity of 28 Btuh/sq ft/F/inch
iNOoo? j
outdoor
]
COMPFT ] COIL 1
SECTION] SECTION {
~~~~~
38HCL
OPER
VOLT*
Max 1 M»r
' 1 ! ;
COMPR ; COMPR М
, О
- tOFM;
^ 1
2 Í i MWA
lra
I
rla
Í
lraírla
I Fui1
227
234
940
; 230/1
960
9Я4 907
72 I 17
88
17 8| 1 5 i 40 8
88
20
94
21 2 : 2 3 i 48 8
FLA — Full Load Amps
LRA — Locked Rotor Amps
MWA — Min imum Wire Amps
OFM — Outdoor Fan Motor
RLA — Rated Load Amps
‘Permissible limits of the voltage range at which the units will operate satisfactorily
NOTES
1 All units have 24-v control circuit which requires external power source
2
Use copper or copper-clad aluminum wire only for compressor section; copper
wire only for outdoor coil section See Installation, Start-Up and Service
Instructions
3
Units require field-supplied grounding wire See Installation, Start-Up and
Service Instructions for wire sizes