1 All 3 outdoor fans must be operating

2 To be used with approved 40RR combinations only
3. Applies to all approved combinations.

Fig. 10 — Cooling Cycle Charging Chart, 40RR/38AQ034

Oil Charge (Table 1

) — Allow unit to run for about

20 minutes. Stop unit and check compressor oil level. Add
oil only if necessary to bring oil into view in sight glass.

Use

only

Carrier-approved

compressor

oil.

Approved

oils are:

Suniso 3GS
Capella B1
DuPont Synthetic
Refrigeration Oil (150 SSU only)

Zerol 150 (synthetic)

Do not reuse drained oil or use any oil that has been

exposed to atmosphere. Procedures for adding or remov­

ing oil are given in Carrier Standard Service Techniques

Manual,Chapter 1, Refrigerants.

If oil is added, run unit for additional 10 minutes. Stop

unit and check oil level. If level is still low, add oil only

after

determining

that

piping

system

is

designed

for

proper oil return and that the system is not leaking oil.

Check Operation

of

all

safety

controls.

Replace

all service panels. Be sure that control panel cover is

closed tightly.