Table 2 — Electrical Data

UNIT

MODEL

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPR

OUTDOOR

FAN

MOTOR

INDOOR

FAN

MOTOR

FACTORY-

INSTALLED

HEATERS

POWER

SUPPLY

Min

Max

RLA

LRA

Qty

FLA

Hp

FLA

FLA

kW

Min Ckt

Amps

MOCP

(Amps)

50DPE014

208/230-3-60

187

253

49 3

191

2

7 7

20
30
20
20
20
20
30
30
30
30

7 5

106

7 5
75
7 5
7 5

106
106
10 6
10 6

74/ 82

122

122/135

41/ 45
74/ 82

122

122/135

41/ 45

26/31

42*

42/52

14/17

26/31

42*

42/52

14/17

85/ 85
88/ 88

102/112

214

162/179

85/ 85

106/116

217

166/182

88/ 88

460-3-60

414

508

22 1

86

2

33

20
30
20
20
20
30
30
30

3 4
48
34
34
34
48
48
48

21

39
66

21

39
66

16

30
51

16
30
51

38

40
38
53
85
40
55
86

575-3-60

518

632

17 9

69

2

26

20
30

20
3.0

2 7
3 9
2 7

3.9

37
37

37
37

31

32
50

52

45
45
50
60

50DP016

208/230-3-60

187

253

61

266

2

77

30

10 5

74/ 82

122/135

163

163/180

26/31

42/52

56*

56/69

103/103
10//116
166/182

217

217/239

)___

460-3-60

414

508

32 0

120

2

33

30

48

39
66
96

30
51
73

48
55
89

126

1

575-3-60

518

632

25 6

96

2

26

30

39

50

49

38
68

70

50DP020

208/230-3-60

187

254

49 3

(ea)

153

(ea)

2

77

50

16 7

74/ 82

122/135
163/180

26/31

42/52
56/69

144/144
144/144

174/190 i

225/246

460-3-60

414

508

199

(ea)

77

(ea)

2

33

50

7 6

39
66
96

30
51
73

59
59
93

130 i

H

Fuse only, unshaded values indicate fuses or circuit

" Siiij breakers may be used

Compr — Compressor
FLA

— Full Load Amps

Hp

— Horsepower

LRA — Locked Rotor Amps
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps

*CSA-approved heaters are rated at 208 volts only