Table 2 — Electrical Data
UNIT
MODEL
VOLTS-PH-HZ
VOLTAGE
RANGE
COMPR
OUTDOOR
FAN
MOTOR
INDOOR
FAN
MOTOR
FACTORY-
INSTALLED
HEATERS
POWER
SUPPLY
Min
Max
RLA
LRA
Qty
FLA
Hp
FLA
FLA
kW
Min Ckt
Amps
MOCP
(Amps)
50DPE014
208/230-3-60
187
253
49 3
191
2
7 7
20
30
20
20
20
20
30
30
30
30
7 5
106
7 5
75
7 5
7 5
106
106
10 6
10 6
74/ 82
122
122/135
41/ 45
74/ 82
122
122/135
41/ 45
26/31
42*
42/52
14/17
26/31
42*
42/52
14/17
85/ 85
88/ 88
102/112
214
162/179
85/ 85
106/116
217
166/182
88/ 88
460-3-60
414
508
22 1
86
2
33
20
30
20
20
20
30
30
30
3 4
48
34
34
34
48
48
48
21
39
66
21
39
66
16
30
51
16
30
51
38
40
38
53
85
40
55
86
575-3-60
518
632
17 9
69
2
26
20
30
20
3.0
2 7
3 9
2 7
3.9
37
37
37
37
31
32
50
52
45
45
50
60
50DP016
208/230-3-60
187
253
61
266
2
77
30
10 5
74/ 82
122/135
163
163/180
26/31
42/52
56*
56/69
103/103
10//116
166/182
217
217/239
)___
460-3-60
414
508
32 0
120
2
33
30
48
39
66
96
30
51
73
48
55
89
126
■
1
575-3-60
518
632
25 6
96
2
26
30
39
50
49
38
68
70
50DP020
208/230-3-60
187
254
49 3
(ea)
153
(ea)
2
77
50
16 7
74/ 82
122/135
163/180
26/31
42/52
56/69
144/144
144/144
174/190 i
225/246
460-3-60
414
508
199
(ea)
77
(ea)
2
33
50
7 6
39
66
96
30
51
73
59
59
93
130 i
H
Fuse only, unshaded values indicate fuses or circuit
" Siiij breakers may be used
Compr — Compressor
FLA
— Full Load Amps
Hp
— Horsepower
LRA — Locked Rotor Amps
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps
*CSA-approved heaters are rated at 208 volts only