beautypg.com

Carrier 50DPE014 User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

10

(J'IFPT

DRAIN CONNECTION^ L

(HALF COUPLING) "V

BASE RAIL-

u

TO TRAP -O'

Fig. 9 — Condensate Drain Piping Details

Step

6

— Make Electrical Connections

FIELD POWER SUPPLY — Unit is factory wired for

voltage shown on nameplate. Units are provided with

terminal block.

When installing units, provide a disconnect per NEC

of adequate size (Table 2).

All field wiring must comply with National Electrical

Code and local requirements.

Route power lines through control box end panel — or

unit basepan — (Fig. 4) to terminal connections as shown

on unit wiring diagram and Fig. 10.

I----------1

TBI

ÜO I

U

z ^ I

o

q

: I

U liJ I

OT a.

o '

I

_____ I

FIELD

11

21

POWER

12

22

SUPPLY

13

23

EQUIP GND

Fig. 10 — Field Power Wiring Connections

Operating voltage to compressor must be within

voltage range indicated on unit nameplate. On 3-phase

units, voltages between phases must be balanced within

2% and the current must be balanced within 10%.

Use the following formula to determine the % voltage

imbalance.
% Voltage Imbalance

100

X

voltage

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 volts

BC = 464 volts

AC = 455 volts

Average Voltage =

452 + 464 + 455

1371

457

Determine maximum deviation from average voltage:
(AB) 457 - 452 = 5 volts

(BC) 464 - 457 = 7 volts

(AC) 457 - 455 = 2 volts
Maximum deviation is 7 volts.

Determine % voltage imbalance:

7

% Voltage Imbalance = 100 x-

457

1.53%

This amount of phase imbalance is satisfactory as it is

below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase im­

balance is more than 2%, contact your local electric

utility company immediately.

Unit failure as a result of operation on improper line

voltage or excessive phase imbalance constitutes abuse

and may cause damage to electrical components. Such

operation would invalidate any applicable Carrier

warranty.

FIELD CONTROL WIRING — Install a Carrier-

approved accessory thermostat assembly according to

installation instructions included with accessory. Locate
thermostat assembly on a solid wall in the conditioned

space to sense average temperature.

Route thermostat cable or equivalent single leads of

no. 18 AWG colored wire from subbase terminals

through conduit in unit to low-voltage connections as

shown on unit label wiring diagram and in Fig. 11.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insu­

lated wire (35 C minimum). For 50 to 75 ft, use no. 16

AWG insulated wire (35 C minimum). For over 75 ft, use

no. 14 AWG insulated wire (35 C minimum).

Set heat anticipator settings as indicated in Table 3.

Settings may be changed slightly to provide a greater

degree of comfort for a particular installation.

Refer to accessory remote control panel instructions

as required.

THERMOSTAT ASSEMBLY

REMOVABLE JUMPER

^ ^ 1^ ^ ^

[

r

] [

b

] É I 1 И Й ] Й Й 1 [

c

] É 1 Q

l

1 [ ] 3 ] @

Q

llJ

q

:

Z)

_l

m

LOW-VOLTAGE TERMINAL BLOCK IN UNIT CONTROL BOX

Fig. 11 — Field Control Thermostat Wiring

Step 7 — Make Outdoor Air Inlet Adjustments

MANUAL OUTDOOR AIR DAMPER — All units

(except those equipped with a factory-installed econo­

mizer) have a manual outdoor air damper to provide

ventilation air. Damper can be preset to admit up to 25%

outdoor air into return air compartment. To adjust,

loosen securing screws and move damper to desired

setting then retighten screws to secure damper (Fig. 12).
OPTIONAL ECONOMIZER
Enthalpy Control Setting (location is shown in Fig. 13) —

For maximum benefit of outside air, set enthalpy control

to the A setting (Fig. 14).

This manual is related to the following products: