beautypg.com

Carrier 50DPE014 User Manual

Page 15

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Economizer Adjustment

1. Set enthalpy control at its highest setting. If outdoor

temperature is above 70 F, perform the following;

install jumper between enthalpy control terminals 1

and 2 (red and yellow wires).

2. Set system selector switch at COOL and set cooling

selector lever at lowest setting. (Cooling mode may be

simulated by removing thermostat wires from termi­

nals Y1 and Y2 [if used] and installing jumper between

Y1 and R.)

3. Set mixed air thermostat (MAT.) at lowest setting.

Outdoor air damper goes to fully open position

(indoor air damper closes).

4. Set mixed air thermostat at highest setting. Outdoor

air damper goes to fully closed position (indoor air

damper opens).

5. Adjust mechanical linkage for correct positioning

if necessary. If cooling was simulated in 2, remove

jumper and reconnect thermostat wire(s).

Power Failure

— Dampers do not have a spring

return. In event of power failure, dampers remain in

position until power is restored. Do not manually

operate damper motor.

50DP020 Indoor Air Fan Motor Removal

NOTE; To remove belts only, follow steps 1 - 4.

1. Remove filter and supply air section access panels.

Remove center post (Fig. 4).

2. Loosen adjusting nuts A and E, Fig. 23.
3. Push motor away from indoor coil to zero adjustment.

Tighten nut A.

4. Remove belts from pulleys.
5. Remove holddown screws at B and C. Loosen screw

at D.

6. Holding motor and pulley securely, slide motor

mount assembly out of unit along slide tracks.

NOTE; To reinstall motor, reverse above procedure.

Refrigerant Charge

— Amount of refrigerant charge

is listed on unit nameplate and in Table 1. Refer to Carrier

Standard Service Techniques Manual, Chapter I,

Refrigerants.

Unit panels must be in place when unit is operating

during charging procedure.

NO CHARGE — Use standard evacuating techniques.

After evacuating system, weigh in the specified amount of

refrigerant. (Refer to Table 1.)

LOW CHARGE COOLING — Using appropriate cool­

ing charging chart. Fig. 24 or 25, add refrigerant until

conditions of the chart are met. Note that charging charts

are different from ones normally used. Charts are based

on charging units to correct superheat for various

operating conditions. An accurate pressure gage and

temperature sensing device are required. Connect tem­

perature sensing device to service port on suction line and

insulate it so that outdoor ambient temperature does not

affect reading. Indoor air cfm must be within normal

operating range of unit.

TO USE COOLING CHARGING CHART — Take

outdoor ambient temperature and read the suction

pressure gage. Refer to ehart to determine correct

suction temperature. If suction temperature is high, add

refrigerant. If suction temperature is low, carefully blow

some of the charge. Recheck suction pressure as charge

is adjusted.

Example; Fig. 24 — 50DPE014

Outdoor Temperature............................................85 F

Suction Pressure.............................................. 75 psig

Suction Temperature should be............................ 60 F

(Suction Temperature may vary ± 5 F.)

If Chargemaster® charging device is used, temperature

and pressure readings must be accomplished using
appropriate charging chart.

Fig. 23 — 50DP020 Indoor Fan Motor Section

Fig. 24 — Cooling Charging Chart —

50DPE014, 50DP016

15

This manual is related to the following products: