COOLING CAPACITIES

50YX018 (IV

2

Tons)

50YX030 (2У2 Tons)

Evap Air

- Cfm/BF

Evap Air - Cfm/BF

Temp (F)

525/0.07

675/0.09

750/0.10

Temp (F)

1000/0.06

1125/0.07

1250/0.08

Air Ent

Evap Air

- Ewb (F)

Cond

Evap Air

- Ewb (F)

72

67

63*

62

72

67

63*

62

72

67

63*

62

72

67

63*

62

72

67

63*

62

72

67

63*

62

TC

20 4 18 б] 174 17 1 21.1 193 180 178 21.3 195 18.2 182

TC

34 8 31 9 29 8 29 4 35 1 32 2 30 1 29 9 35 6 32 7 30.5 30.8

85 SHC

10.2 12.9 12.6 15.6 11.2 14.5 14.1 17.6 11.6 15.3 14.8 18.2

85 SHC

18.1 23.5 22.8 28.5 18.9 24.8 24.1 29.9 19.7 26.3 25.3 30.8

kW

1.60 1.58 1.58 1.57 1.64 1.63 1.62 1.62 1.66 1.65 1.64 1.64

kW

2.66 2.63 2.62 2.61 2.70 2.68 2.66 2.66 2.75 2.73 2.71 2.72

TC

196 179 167 164 20.2 185 173 17.2 20 3 187 174 176

TC

33.5 30 7 28.6 28.3 33 8 31 0 28.9 29.0 34.3 31 5 29.3 29 8

95 SHC

9.94 126 12.3 15.3 10.9 142 13.8 17.2 11 3 15.0 14.5 176

95 SHC

17.6 23.0 22.3 27.9 18.4 24 4 23.6 29 0 19.3 25.8 24 8 29 8

kW

1.76 1.74 1.73 1.73 1.80 1.78 1.77 1.77 1.82 1.80 1.79 1.79

kW

2.89 2.87 2.85 2.84 2.94 2.91 2.90 2.90 3.00 2.97 2.94 2.95

TC

187 17.2 16.0 15.7 19.3 177 165 166 19 5 17.9 166 170

TC

32.1 29.4 27.4 27 2 32.7 29.7 27.7 28 0 32 9 30 2 28 0 28 7

105 SHC

9 62 12.3 120 14.9 106 13.9 13.5 166 11 0 147 14.2 170

105 SHC

17 1 22.5 21.8 27 2 18.0 23.9 23 1 28.0 188 25.3 24.3 28.7

kW

1.92 1.91 1.89 1.89 1.97 1.95 1.94 1.94 1.99 1.97 1.96 1.96

kW

3.16 3.13 3 11 3.10 3.22 3 18 3.16 3.16 3.26 3.23 3.21 3.21

TC

17.9 164 152 150 184 169 156 159 185 170 158 163

TC

30 7 28 2 26 2 26 3 31.2 28.4 26.5 27.0 31 4 28.8 26 8 27.7

115 SHC

9 31 120 11 6 145 10.3 136 13 1 159 107 144 138 163

115 SHC

16.7 22.0 21.3 26.3 175 23.4 22.5 27.0 18.3 24.8 23 8 27.7

kW

2 11 2.09 2 07 2 07 2 16 2 14 2 12 2.13 2 17 2.16 2 14 2.14

kW

3 45 3.42 3 40 3 40 3 51 3.47 3 44 3 45 3 56 3 53 3 50 3 51

50Y X024 (2 Tons)

.....--------

— —

-

50YX036 (3 Tons)

- --

Evap Air - Cfm/BF

Evap Air - Cfm/BF

Temp (F)

800/0.05

900/0.05

1000/0.06

Temp (F)

1200/0.13

1350/0.14

1500/0.16

Air Ent

Evap Air

- Ewb (F)

Cond

Evap Air - Ewb (F)

72

67

63*

62

72

67

63*

62

72

67

63*

62

72

67

63*

62

72

67

63*

62

72

67

63*

62

TC

27 9 25 6 23 8 23 5 28 2 25.8 24.1 24 0 28 5 26 0 24.3 24.6

TC

40 3 36 8 34 3 33 8 40 6 37.3 34.8 34 5 41 0 37.6 35.1 35.1

85 SHC

146 189 183 23 0 152 20 1 194 24.0 15.9 21.2 20.4 24.6

85 SHC

20.7 26 7 25 9 32.3 21.5 28 2 27 3 34 0 22.3 29.6 28.7 35 1

kW

2.12 2.12 2.12 2.12 2.16 2.16 2.16 2.16 2.20 2.19 2.19 2.19

kW

3.17 3.13 3.10 3.09 3.21 3.19 3.16 3.15 3.27 3.24 3.22 3.21

TC

26 8 24 5 22 7 22 6 27 1 24.8 23 1 23 3 27 3 25 0 23 3 23.8

TC

38.6 35.4 33 0 32.6 39.1 35 8 33.4 33 2 39 5 36 1 33.7 34 0

95 SHC

142 185 179 22 5 14.8 19.7 190 23 3 15.5 20.8 20.0 23.8

95 SHC

20.1 26.1 25.3 31.6 21.0 27.6 26.7 33.1 21.8 29.0 28.1 34.0

kW

2.34 2.33 2.33 2.33 2.37 2.37 2.37 2.37 2.41 2.41 2.40 2.40

kW

3 47 3.43 3.40 3.40 3.53 3.48 3.46 3.46 3.58 3.54 3.52 3.52

TC

25.7 23 5 21.7 21.8 26 0 23 8 22.1 22.5 26 1 23.9 22 3 23 0

TC

37.0 33.9 31.6 31 3 37.4 34.3 32.0 32 0 37 7 34 5 32 2 32.8

105 SHC

13.8 18.1 17.5 21.8 145 19.3 18.6 22.5 15.1 20.4 19.6 23.0

105 SHC

19.5 25.6 24.7 30.8 20.4 27.0 26.1 32.0 21.2 28.4 27.4 32.8

kW

2.58 2.57 2.56 2.57 2.61 2.61 2.61 2.61 2.65 2.64 2.64 2.64

kW

3.80 3.77 3.74 3.73 3.85 3 82 3.80 3.80 3.91 3.87 3.85 3.86

TC

24 5 22 4 20 8 20 9 24 6 22 6 21 1 21 5 24 8 22.9 21 3 22 1

TC

35.4 32 4 30.1 29 9 35.7 32.7 30 4 30 7 35 8 32 9 30 6 31.4

115 SHC

13.4 177 17.1 20.9 14.0 18.8 18.2 21 5 147 199 192 22 1

115 SHC

19.0 25 0 24.1 29 9 19.8 26 4 25 4 30.7 20.6 27.8 26 7 31.4

kW

2 84 2.83 2 83 2 83 2 87 2.87 2 87 2 86 2.91 2 91 2.91 2.91

kW

4.18 4 14 4.10 4 10 4.24 4.19 4 15 4 17 4 27 4 24 4 20 4 22

LEGEND

BF

— Bypass Factor

Edb

— Entering Dry-Bulb

Ewb

— Entering Wet-Bulb

kW

— Total Unit Power Input

Ldb

— Leaving Dry-Bulb

Lwb

— Leaving Wet-Bulb

SHC

— Sensible Heat Capacity (1000 Btuh) Net

TC

— Total Capacity (1000 Btuh) Net

*At 75 F entering dry bulb (Tennessee Valley Authority [TVA] rating con­

ditions); all others at 80 F entering dry bulb.

NOTES:

1 Direct interpolation is permissible. Do not extrapolate

2 The following formulas may be used:

sensible capacity (Btuh)

= *edb

1

loxcfm

t|wb = Wet-bulb temperature corresponding to enthalpy of air leaving

evaporator coil (h|y^,b)

total capacity (Btuh)

^Iwb “ ^wb

4 5

X cfm

Where: hg^^jj = Enthalpy of air entering evaporator coil

The SHC Is based on 80 F edb temperature of air entering evaporator
coil

Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

Correction Factor = 1 10 x (1 - BF) x (edb - 80)