SINGLE POINT BOX ELECTRICAL DATA
UNIT
SIZE
BASE
UNIT
BASE
UNIT
UNIT
FUSE
ELECTRIC
HEATER kW AT
ELECTRIC
HEATER
ELECTRIC
HEATER
ELECTRIC
HEATER
TOTAL MCA
(Base Unit
and Electric
Heater)
SINGLE
POINT BOX
50YX
V-PH
MCA
SIZE
208 V
240 V
V-PH
MCA
FUSE SIZE
PART NO.
3.75
50
22 5/26 0
25/30
39 1/ 42 6
50YX-900—001
018
208/230-1
16.6
25
5.6
75
208/240-1
33.8/39 1
35/40
50 4/ 55 7
5ÒYX-900—002
75
100
45.1/52.0
50/60
61 7/ 68.6
50YX-900—002
3 75
5.0
22.5/26.0
25/30
43.5/ 47.0
50YX-900—001
024
208/230-1
21.0
30
56
75
208/240-1
33.8/39.1
35/40
54 8/ 60 1
50YX-900—002
75
10.0
45.1/52 0
50/60
66 1/ 73 0
50YX-900—002
3.75
5.0
22.5/26 0
25/30
47.0/ 50 5
50YX-900—002
030
208/230-1
24.5
35
56
7.5
208/240-1
33.8/39 1
35/40
58.3/ 63 6
50YX-900—003
75
10.0
45.1/52 0
50/60
69 6/ 76 5
50YX-900—003
11.3
15.0
67.6/78.1
70/80
92.1/102 6*
50YX-900—004
3 75
5.0
22.5/26.0
25/30
53 2/ 56.7
50YX-900—002
208/230-1
56
7.5
208/240-1
33 8/39.1
35/40
64 5/ 69.8
50YX-900—003
036
30.7
50
7 5
100
45 1/52.0
50/60
75 8/ 82.7
50YX-900—003
11 3
' 15.0
67 6/78.1
70/80
98.3/108.8*
50YX-900—004
208-1**
15.0
-
208-1**
90 1
100
120.8t
50YX-900—004
3 75
5.0
22.5/26.0
25/30
55 7/ 59.2
50YX-900—002
208/230-1
5.6
75
208/240-1
33.8/39.1
35/40
67 0/ 72.3
50YX-900—003
042
33 2
50
7 5
100
45.1/52.0
50/60
78.3/ 85 2
50YX-900—003
11.3
150
67 6/78.1
70/80
100.8*/111.3*
50YX-900—004
208-1**
150
-
208-1**
90.1
100
123.3t
50YX-900—004
3.75
50
208/240-1
22 5/26.0
25/30
62.4/ 65 9
50YX900—002
5.6
75
208/240-1
33.8/39.1
35/40
73 7/113 6
50YX900-003
048
208/230-1
39 9
60
7.5
100
208/240-1
45 1/52.0
50/60
85 0/ 91 9
50YX900—003
11.3
15.0
208/240-1
67 6/78.1
70/80
107.5*/147 4t
50YX900—004
15.0
-
208-1**
90.1
100
139.9t
50YX900—004
8.75
50
208/240-1
22 5/26.0
25/30
72.3/ 75.8
50YX900—002
5.6
7.5
208/240-1
33.8/39.1
35/40
83.6/ 88.9
50YX900—003
060
208/230-1
49 8
60
7.5
10.0
208/240-1
45.1/52.0
50/60
94 9/101.8*
50YX900—003
11.3
150
208/240-1
67 6/78 1
70/80
117.4t/127.9t
50YX900—004
150
-
208-1**
90.1
100
139.8
50YX900—004
LEGEND
AWG
— American Wire Gage
MCA
— Minimum Circuit Amps
NEC
— Nationai Eiectricai Code
UL
— Underwriters’ Laboratories
*75 C copper conductor required.
t90 C copper conductor required
**For 208-v usage only.
NOTES:
1. Maximum field wire size should be no. 2 AWG.
2. All ampacities above (unless otherwise noted) will allow use of a
60 C copper conductor at 86 F ambient temperature.
3. All values shown for MCA and fuses are calculated per UL 1995 and
comply with the NEC.
4. Single point boxes are not available for 25 kW electric heaters.
14